3 behavior when faults are removed – JLG TF6-42 Service Manual Manuale d'uso
Pagina 206

17
2.3 Behavior when faults are removed
2.3.1 Over Voltage
Normal operation is resumed.
2.3.2 Under Voltage
Not applicable.
2.3.3 Internal Faults
Not applicable.
2.3.4 Program Out of Control
Not applicable.
2.3.5 Intermittent Power Loss
Not applicable.
2.3.6 Single Faults on Outputs
In Platform Control Mode, once SHUTDOWN is entered, the fault must be removed and the controller
must be reset to regain drive again.
In other normal driving modes, after the fault is removed, normal operation is resumed.
2.3.7 Multiple Faults on Related Outputs
In AWP Mode, once SHUTDOWN is entered, the fault must be removed and the controller must be
reset to regain drive again.
In other modes, the APC160 remains in SHUTDOWN mode until all faults but one are resolved, at
which time, the controller resumes operation as described with single faults. In any case, the
transmission is forced to Neutral until the shift lever (or joystick when in Platform Control Mode) is
cycled through Neutral.
2.3.8 Incorrect Input Patterns
Normal operation is resumed.
2.3.9 Speed Sensor Fault
In AWP Mode, once SHUTDOWN is entered, the fault must be removed and the controller must be
reset to regain drive again.
Normal operation is resumed. Exit from limp-home always occurs through Neutral.
2.3.10 Analog Sensor Fault
Normal operation is resumed.