Campomatic C64BC Manuale d'uso
Pagina 45

TEST MODE
With the blast chiller switched off, press buttons 1 and 3 at the
same time, then 1 and 5; if no button is pressed, after seconds
the system exits the test mode.
In the test mode:
- button 1 activates the compressor and switches on icon 10.
- button 2 activates the condenser fan and switches on icon
11.
- button 3 activates the evaporator fan and switches on icon
12.
If the door is open, icon 7 is activated.
If the chamber probe is malfunctioning, icon 14 is activated.
If the food probe is malfunctioning, icon 9 is activated.
ALARM INDICATIONS
Interruption due to low yield:
icon n° 8
Interruption due to core probe:
icon n° 9
Interruption due to voluntary interruption:
icon n° 13
Interruption due to chamber probe:
icon n° 14
Interruption due to open door:
icon n° 15
Interruption due to blackout:
icon n° 16
41