SETTABLE PARAMETERS
The following parameters which can be set by the PC have
been coded (note: the hysteresis works apart from the set
parameter, which means a setting of -30 hysteresis 4 indicates
that the appliance cuts-off at -30 and switches back on at -26).
1) set deep-freezing temperature. From -10 to -35 default -30
2) deep-freeze hysteresis. From 0.5 to 7 default 4
3) deep-freezing maintenance temperature. From -10 to -35
default -20
4) deep-freezing maintenance hysteresis. From 0.5 to 7 default
4
5) blast chiller set temperature From -10 to -35 default -30
6) blast chiller hysteresis. From 0.5 to 7 default 4
7) blast chiller maintenance temperature From 3 to -35 default
1°
8) blast chiller maintenance hysteresis From 0.5 to 7 default 4
9) set bottle temperature. From 3 to -35 default -30
10) bottle hysteresis. From 0.5 to 7 default 4
11) can set temperature From 3 to -35 default -30
12) can hysteresis. From 0.5 to 7 default 4
13) blast chiller duration (the time is calculated by dividing this
maximum time into sections) From 1 to 255 default 180
14) deep-freeze duration (the time is calculated by dividing
this maximum time into sections) From 1 to 255 default 240
15) threshold to be met to check the blast chiller yield -20 to -
30 default -26
16) threshold to be met to check the deep freeze yield -20 to -
30 default -26
17) can duration 1 to 255 default 30
18) bottle duration 1 to 255 default 30
19) percentage of time for checking the yield from 10 to 100%
20) can maintenance temperature. From 10 to 0 default 3
21) bottle maintenance temperature. From 15 to 0 default 8