EVCO EPU2LXP1CP Manuale d'uso
Pagina 97

Evco S.p.A.
c-pro 3 micro HPRU | Manuale utente ver. 2.0 | Codice 144CP3UHI204
pagina 97 di 120
0x06C2 1731 Pr24_DelayResistenzaACS
30
0
999
R/W
0x06C3 1732 PV01_SHsetpoint1
6.0
3.0
25.0
R/W
0x06C4 1733 PV02_LoSHsetpoint1
2.0
1.0
3.0
R/W
0x06C5 1734 PV03_HiSHsetpoint1
15.0
10.0
40.0
R/W
0x06C6 1735 PV04_LOPtemp1
-40.0
-40.0
40.0
R/W
0x06C7 1736 PV05_MOPtemp1
40.0
-40.0
40.0
R/W
0x06C8 1737 PV06_PIDpropBand1
7.0
1.0
100.0
R/W
0x06C9 1738 PV07_PIDintegralTime1
120
0
999
R/W
0x06CA 1739 PV08_PIDderivTime1
120
0
999
R/W
0x06CB 1740 PV09_StartUpDelay1
5
1
255
R/W
0x06CC 1741 PV10_StartUpPosition1
50.00
0.00
100.00
R/W
0x06CD 1742 PV11_SHsetpoint2
6.0
3.0
25.0
R/W
0x06CE 1743 PV12_LoSHsetpoint2
2.0
1.0
3.0
R/W
0x06CF
1744 PV13_HiSHsetpoint2
15.0
10.0
40.0
R/W
0x06D0 1745 PV14_LOPtemp2
-40.0
-40.0
40.0
R/W
0x06D1 1746 PV15_MOPtemp2
40.0
-40.0
40.0
R/W
0x06D2 1747 PV16_PIDpropBand2
7.0
1.0
100.0
R/W
0x06D3 1748 PV17_PIDintegralTime2
120
0
999
R/W
0x06D4 1749 PV18_PIDderivTime2
120
0
999
R/W
0x06D5 1750 PV19_StartUpDelay2
5
1
255
R/W
0x06D6 1751 PV20_StartUpPosition2
50.00
0.00
100.00
R/W
0x06D7 1752 PV21_StabilizationDelay
0
0
255
R/W
0x06D8 1753 PV22_SabilizationPosition
100.00
0.00
100.00
R/W
0x06D9 1754 PV23_FunctioningMode
0
0
1
R/W
0x06DA 1755 PV24_ManualValvePositionSetPoint
0.00
0.00
100.00
R/W
0x06DB 1756 PV25_SHcontrolParametersSet
0
0
1
R/W
0x06DC 1757 PV26_RelayFuncSel
6
0
255
R/W
0x06DD 1758 PV27_AIV3probeType
0
0
1
R/W
0x06DE 1759 PV28_AIV4probeType
2
0
5
R/W
0x06DF 1760 PV31_TsTemperatureOffset
0.0
-10.0
10.0
R/W
0x06E0
1761 PV32_TeTemperatureOffset
0.0
-10.0
10.0
R/W
0x06E1
1762 PV34_RelayLogic
0
0
1
R/W
0x06E2
1763 PV35_DI1Logic
0
0
1
R/W
0x06E3
1764 PV36_DI2Logic
0
0
1
R/W
0x06E4
1765 PV37_DIHVLogic
0
0
1
R/W
0x06E5
1766 PV60_enabSHmod
1
0
1
R/W
0x06E6
1767 PV61_maxSetSH
15.0
3.0
25.0
R/W