2 parametri con driver integrato – EVCO EPU2LXP1CP Manuale d'uso
Pagina 86

Evco S.p.A.
c-pro 3 micro HPRU | Manuale utente ver. 2.0 | Codice 144CP3UHI204
pagina 86 di 120
15.2
Parametri con driver integrato
PARAMETRI EVCM (CO-V)
PV01
Setpoint SH (1)
6.0
10.8
3.0
5.4
25.0
45.0
K
R
CO-V
PV02
Setpoint LoSH (1)
2.0
3.6
1.0
1.8
3.0
5.4
K
R
CO-V
PV03
Setpoint HiSH (1)
15.0
27.0
10.0
18.0
40.0
72.0
K
R
CO-V
PV04
Setpoint LOP (1)
-40.0
-72.0
-40.0
-72.0
40.0
72.0
K
R
CO-V
PV05
Setpoint MOP (1)
40.0
72.0
-40.0
-72.0
40.0
72.0
K
R
CO-V
PV06
PID – banda proporzionale (1)
7.0
12.6
1.0
1.8
100.0
180.0
K
R
CO-V
PV07
PID – tempo integrale (1)
120
0
999
sec
CO-V
PV08
PID – tempo derivativo (1)
120
0
999
sec
CO-V
PV09
Start-up delay (1)
5
1
255
sec
CO-V
PV10
Start-up position (1)
50.00
0.00
100.00
%
CO-V
PV11
Setpoint SH (2)
6.0
10.8
3.0
5.4
25.0
45.0
K
R
CO-V
PV12
Setpoint LoSH (2)
2.0
3.6
1.0
1.8
3.0
5.4
K
R
CO-V
PV13
Setpoint HiSH (2)
15.0
27.0
10.0
18.0
40.0
72.0
K
R
CO-V
PV14
Setpoint LOP (2)
-40.0
-72.0
-40.0
-72.0
40.0
72.0
K
R
CO-V
PV15
Setpoint MOP 2)
40.0
72.0
-40.0
-72.0
40.0
72.0
K
R
CO-V
PV16
PID – banda proporzionale (2)
7.0
12.6
1.0
1.8
100.0
180.0
K
R
CO-V
PV17
PID – tempo integrale (2)
120
0
999
sec
CO-V
PV18
PID – tempo derivativo (2)
120
0
999
sec
CO-V
PV19
Start-up delay (2)
5
1
255
sec
CO-V
PV20
Start-up position (2)
50.00
0.00
100.00
%
CO-V
PV21
Tempo stabilizzazione
0
0
255
sec
CO-V
PV22
Posizione stabilizzazione
100.00
0.00
100.00
%
CO-V
PV23
Modo funzionamento:
0= SH algo
1= Manual
0
0
1
CO-V
PV24
Posizione manuale
0.00
0.00
100.00
%
CO-V
PV25
Set Parametri SH:
0= set1
1= set2
0
0
1
CO-V
PV26
Posizione di stand-by
0.00
0.00
100.00
%
CO-V
PV27
Posizione in caso di allarme
0.00
0.00
100.00
%
CO-V