EVCO EPU2LXP1CH Installer manual Manuale d'uso
Pagina 40

EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page40 of122
PV45
Setpoint MOP (1)
40.0
-40.0
40.0
K
CO-V
PV46
PID – banda proporzionale (1)
7.0
1.0
100.0
K
CO-V
PV47
PID –tempo integrale (1)
120
0
999
sec
CO-V
PV48
PID –tempo derivativo (1)
120
0
999
sec
CO-V
PV49
Ritardo avvio (1)
5
1
255
sec
CO-V
PV50
Posizione avvio (1)
50.00
0.00
100.00
%
CO-V
PV51
Setpoint SH (2)
6.0
3.0
25.0
K
CO-V
PV52
Setpoint LoSH (2)
2.0
1.0
3.0
K
CO-V
PV53
Setpoint HiSH (2)
15.0
10.0
40.0
K
CO-V
PV54
Setpoint LOP (2)
-40.0
-40.0
40.0
K
CO-V
PV55
Setpoint MOP 2)
40.0
-40.0
40.0
K
CO-V
PV56
PID –banda proporzionale (2)
7.0
1.0
100.0
K
CO-V
PV57
PID –tempo integrale (2)
120
0
999
sec
CO-V
PV58
PID –tempo derivativo (2)
120
0
999
sec
CO-V
PV59
Ritardo avvio (2)
5
1
255
sec
CO-V
PV60
Posizione avvio (2)
50.00
0.00
100.00
%
CO-V
PV61
Tempo stabilizzazione
0
0
255
sec
CO-V
PV62
Posizione stabilizzazione
100.00
0.00
100.00
%
CO-V
PV63
Modo funzionamento:
0= Algo SH
1= Manuale
0
0
1
CO-V
PV64
Posizione manuale
0.00
0.00
100.00
%
CO-V
PV65
Set parametri SH:
0= set1
1= set2
0
0
1
CO-V
PV66
Funzione relè:
0= Disabilitato
1= Abilitato: qualsiasi allarme
2= Abilitato: errore sonda
3= Allarme LoSH
4= Allarme MOP
5= Allarme valvola
6= Valvola solenoide
7= Valvola solenoide + allarmi
8= Risincronizzazione
6
0
8
CO-V
PV67
Tipo sonda 3:
0= NTC
1= PT1000
0
0
1
CO-V
PV68
Tipo sonda 4:
0= 4..20mA (0.5 – 8)
1= 4..20mA (0 – 30)
2= 0-5V (0 – 7)
3= 0-5V (0 – 25)
4= 0-5V (0 – 60)
5= scaling
0
0
1
CO-V
PV69
Tipo sonda 1:
1= PTC
2= NTC
3= 0..20mA
4= 4..20mA
5= 0-5V
6= 0-10V
7= PT1000
5
1
9
CO-V