EVCO EPU2LXP1CH Installer manual Manuale d'uso
Pagina 38

EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page38 of122
HD09
controllore
14
26
6
22
0
0
0
HD10
…
HD18
Impostano quali risorse digitali
collegare alle uscite digitali
dell’espansione
30
32
40
0
0
0
0
0
0
0
48
CO-
HW
MODULI VALVOLE ELETTRONICHE
EVDRIVE03 circuito 1
PV01
Setpoint SH (1)
6.0
3.0
25.0
K
CO-V
PV02
Setpoint LoSH (1)
2.0
1.0
3.0
K
CO-V
PV03
Setpoint HiSH (1)
15.0
10.0
40.0
K
CO-V
PV04
Setpoint LOP (1)
-40.0
-40.0
40.0
K
CO-V
PV05
Setpoint MOP (1)
40.0
-40.0
40.0
K
CO-V
PV06
PID – banda proporzionale (1)
7.0
1.0
100.0
K
CO-V
PV07
PID – tempo integrale (1)
120
0
999
sec
CO-V
PV08
PID – tempo derivativo (1)
120
0
999
sec
CO-V
PV09
Ritardo avvio (1)
5
1
255
sec
CO-V
PV10
Posizione avvio (1)
50.00
0.00
100.00
%
CO-V
PV11
Setpoint SH (2)
6.0
3.0
25.0
K
CO-V
PV12
Setpoint LoSH (2)
2.0
1.0
3.0
K
CO-V
PV13
Setpoint HiSH (2)
15.0
10.0
40.0
K
CO-V
PV14
Setpoint LOP (2)
-40.0
-40.0
40.0
K
CO-V
PV15
Setpoint MOP 2)
40.0
-40.0
40.0
K
CO-V
PV16
PID – banda proporzionale (2)
7.0
1.0
100.0
K
CO-V
PV17
PID – tempo integrale (2)
120
0
999
sec
CO-V
PV18
PID – tempo derivativo (2)
120
0
999
sec
CO-V
PV19
Ritardo avvio (2)
5
1
255
sec
CO-V
PV20
Posizione avvio (2)
50.00
0.00
100.00
%
CO-V
PV21
Tempo stabilizzazione
0
0
255
sec
CO-V
PV22
Posizione stabilizzazione
100.00
0.00
100.00
%
CO-V
PV23
Modo funzionamento:
0= Algo SH
1= Manuale
0
0
1
CO-V
PV24
Posizione manuale
0.00
0.00
100.00
%
CO-V
PV25
Set parametri SH:
0= set1
1= set2
0
0
1
CO-V
PV26
Funzione relè:
0= Disabilitato
1= Abilitato: qualsiasi allarme
2= Abilitato: errore sonda
3= allarme LoSH
4= allarme MOP
6
0
8
CO-V