EVCO c-pro kilo AHU Manuale d'uso
Pagina 86

C-PRO KILO AHU MANUALE APPLICATIVO
Pag. 86
0x0674
1653
PH08_EnableChangeMode_DI
1
0
1
R/W
0x0675
1654
PH09_Enable_OnOffBySuperv
0
0
1
R/W
0x0676
1655
PH10_EnableChangeMode_SUP
0
0
1
R/W
0x0677
1656
PH11_Modbus_Address
1
1
247
R/W
0x0678
1657
PH12_Modbus_Baud
3
0
4
R/W
0x0679
1658
PH13_Modbus_Parity
2
0
2
R/W
0x067A
1659
PH14_Modbus_StopBit
0
0
1
R/W
0x067B
1660
PH15_RestoreDefault
0
0
1
R/W
0x067C
1661
PH18_HistoryReset
0
0
1
R/W
0x067D
1662
PH25_EnableOffsetSP_DI
0
0
1
R/W
0x067E
1663
PH26_EnableOffsetSP_SUP
0
0
1
R/W
0x067F
1664
PH27_EnableUniqueSetPoint
0
0
1
R/W
0x0680
1665
PH28_EnableNightTimeBand
0
0
1
R/W
0x0681
1666
PH32_TemperatureUM
0
0
1
R/W
0x0682
1667
PH34_AtmosphericPressure
1013
0
10000
hPa
R/W
0x0683
1668
PH37_MinPPM_QualityAir
0
0
10000
R/W
0x0684
1669
PH38_MaxPPM_QualityAir
2000
0
10000
R/W
0x0685
1670
PH40_EnableExternalProbe
1
0
1
R/W
0x0686
1671
PH41_EnableHumidityEnvironmentProbe
1
0
2
0=Disable,
1=4..20mA,
2=0..5V
R/W
0x0687
1672
PH42_EnableAirExaustProbe
1
0
1
R/W
0x0688
1673
PH43_EnableAntifreezeProbe
0
0
1
R/W
0x0689
1674
PH45_EnablePreHeatingProbe
0
0
1
R/W
0x068A
1675
PH46_EnableAirQualityProbe
0
0
2
0=Disable,
1=4..20mA,
2=0..5V
R/W
0x068B
1676
PH47_EnableHumidityExternalProbe
0
0
2
0=Disable,
1=4..20mA,
2=0..5V
R/W
0x068C
1677
PH50_Logic_DI_OnOff_SP_Mode_Remote
0
0
1
R/W
0x068D
1678
PH51_Logic_DI_Alarm
0
0
1
R/W
0x068E
1679
PH52_Logic_DI_AlarmAirflow
1
0
1
R/W
0x068F
1680
PH53_Logic_DI_AlarmFire
1
0
1
R/W
0x0690
1681
PH60_Logic_DO_Alarm
0
0
1
R/W
0x0691
1682
PG00_UnitType
3
1
6
1=Only Heat, 2=Only
Cool, 3=Heat/Cool +
Humid, 4=Heat/Cool +
R/W