EVCO c-pro kilo AHU Manuale d'uso
Pagina 83

C-PRO KILO AHU MANUALE APPLICATIVO
Pag. 83
0x0615
1558
PM12_PumpCool_Hours ( Low )
0
0
100000
R/W
0x0616
1559
PM12_PumpCool_Hours ( High )
0x0617
1560
PM20_EnManual_Fan
0
0
1
R/W
0x0618
1561
PM21_ForceFans
0.00
0.00
100.00
R/W
0x0619
1562
PM80_Calibration_EnvironmentProbe
0.0
-18.0
18.0
R/W
0x061A
1563
PM81_Calibration_AirSupplyProbe
0.0
-18.0
18.0
R/W
0x061B
1564
PM82_Calibration_AirExternalProbe
0.0
-18.0
18.0
R/W
0x061C
1565
PM83_Calibration_HumidityEnvironment_
Probe
0
-10
10
R/W
0x061D
1566
PM84_Calibration_AirExaustProbe
0.0
-18.0
18.0
R/W
0x061E
1567
PM85_Calibration_AntifreezeProbe
0.0
-18.0
18.0
R/W
0x061F
1568
PM87_Calibration_PreHeatingProbe
0.0
-18.0
18.0
R/W
0x0620
1569
PM88_Calibration_AirQuality_Probe
0
-100
100
R/W
0x0621
1570
PM89_Calibration_HumidityExternal_Probe
0
-10
10
R/W
0x0622
1571
PM90_LastMaintainDATE ( Low )
R/W
0x0623
1572
PM90_LastMaintainDATE ( High )
0x0624
1573
PC01_EnableSetPointCompensation
0
0
1
R/W
0x0625
1574
PC02_MaxSetPoint_Compensation
28.0
-15.0
158.0
R/W
0x0626
1575
PC03_SetPointExternal_StartCompensation
26.0
-15.0
158.0
R/W
0x0627
1576
PC04_OffsetSetPointExternal_Compensatio
n
4.0
0.0
36.0
R/W
0x0628
1577
PC05_Enable_SniffingMode
0
0
1
R/W
0x0629
1578
PC06_WaitTime_SniffingCycle
6
1
99
Minute
R/W
0x062A
1579
PC07_ActiveTime_SniffingCycle
2
1
30
Minute
R/W
0x062B
1580
PC08_EnableBothFans_onSniffing
0
0
1
R/W
0x062C
1581
PF01_FanRegulationType
3
0
3
0=Continue, 1=On/Off,
2=Inverter,
3=Inverter+On/Off
R/W
0x062D
1582
PF02_FanRegulation_Diff
5.0
0.0
36.0
R/W
0x062E
1583
PF03_MinSpeedFan
0.00
0.00
100.00
R/W
0x062F
1584
PF04_MaxSpeedFan
100.00
0.00
100.00
R/W
0x0630
1585
PF05_Fan_TonOther
20
0
999
R/W
0x0631
1586
PF08_FanRegulation_InverterOnOff_Diff
8.00
0.00
60.00
R/W
0x0632
1587
PF09_FanRegulation_InverterOnOff_Time
10
0
999
R/W
0x0633
1588
PF10_ForceOnErrorProbe
30.00
0.00
100.00
R/W
0x0634
1589
Pb01_Temperature_Diff_Valve
10.0
0.0
36.0
R/W