EVCO c-pro kilo AHU Manuale d'uso
Pagina 84

C-PRO KILO AHU MANUALE APPLICATIVO
Pag. 84
0x0635
1590
Pb02_Valve_Ti
0
0
999
R/W
0x0636
1591
Pb03_NeutralZone_Temperature
4.0
0.0
36.0
R/W
0x0637
1592
Pb05_Offset_ValveSupplySetPoint
0.0
0.0
36.0
R/W
0x0638
1593
Pb06_Diff_ValveSupplySetPoint
5.0
0.0
36.0
R/W
0x0639
1594
Pb10_ForceHeatValve_OnErrorProbe
30.00
0.00
100.00
R/W
0x063A
1595
Pb11_ForceCoolValve_OnErrorProbe
30.00
0.00
100.00
R/W
0x063B
1596
Pb20_ResistorOnOffDelayTime
60
0
999
R/W
0x063C
1597
PU02_NeutralZone_Humidity
6
0
100
R/W
0x063D
1598
PU03_Humidity_Diff
10
0
100
R/W
0x063E
1599
PU04_ValveDeHumidification_Ti
0
0
999
R/W
0x063F
1600
PU05_EnLimitDeHumid
0
0
1
R/W
0x0640
1601
PU10_tSupply_EnableHumidifier_Enable
1
0
1
R/W
0x0641
1602
PU11_tSupply_EnableHumidifier_Set
22.0
-15.0
158.0
R/W
0x0642
1603
PU12_tSupply_EnableHumidifier_Diff
3.0
0.0
68.0
R/W
0x0643
1604
PS01_Type_FreeCoolingHeating
1
0
2
0=Disable,
1=Temperature,
2=Entalphy
R/W
0x0644
1605
PS02_EnableAirQualityControl
0
0
1
R/W
0x0645
1606
PS03_Type_ControlShutter
0
0
3
0=FreeCooling/Heatin
g, 1=AirQuality,
2=Maggiore 3=Media
R/W
0x0646
1607
PS05_MinRegulationValue_AirExternalShu
tter
0.00
0.00
100.00
R/W
0x0647
1608
PS06_MaxRegulationValue_AirExternalShu
tter
100.00
0.00
100.00
R/W
0x0648
1609
PS07_RunningTime_AirExternalShutter
120
0
3600
Sec
R/W
0x0649
1610
PS08_EndRunMaximumSignalTime_AirExt
ernalShutter
5
0
600
R/W
0x064A
1611
PS09_MinVariation_AirExternalShutter
0.00
0.00
20.00
%
R/W
0x064B
1612
PS10_FixRegulationValue_AirExternalShut
ter
50.00
0.00
100.00
R/W
0x064C
1613
PS12_FreeCoolingHeatingTemp_enDiff
2.0
0.0
36.0
R/W
0x064D
1614
PS13_FreeCoolingHeatingTemp_enSetPoint
4.0
0.0
68.0
R/W
0x064E
1615
PS15_FreeCoolingHeatingEntalphy_enDiff
8.0
0.0
100.0
R/W
0x064F
1616
PS16_FreeCoolingHeatingEntalphy_enSetP
oint
10.0
0.0
200.0
R/W
0x0650
1617
PS20_AirQuality_SetPoint
600
0
10000
R/W
0x0651
1618
PS21_AirQuality_Diff
100
0
2000
R/W