EVCO c-pro kilo AHU Manuale d'uso
Pagina 81

C-PRO KILO AHU MANUALE APPLICATIVO
Pag. 81
Bit10=AL10,
Bit11=AL11,
Bit12=AL12,
Bit13=AL13,
Bit14=AL14,
Bit15=AL15,
Bit16=AL16
0x0301
770
PackedAlarm_2
0
0
65535
Bit1=AL17,
Bit2=AL18,
Bit3=AL19,
Bit4=AL20,
Bit5=AL21,
Bit6=AL22,
Bit7=AL23, Bit8=Free,
Bit9=AL25,
Bit10=AL26,
Bit11=AL27,
Bit12=AL28,
Bit13=AL29
R/W
0x0400
1025
Status_OnOff_bySUP
0
0
1
R/W
0x0401
1026
Status_MOde_bySUP
0
0
1
R/W
0x0402
1027
Status_En_OffsetSP_bySUP
0
0
1
R/W
0x0500
1281
CLOCK_RTC ( Low )
0
0
2147483
647
R/W
0x0501
1282
CLOCK_RTC ( High )
0x0502
1283
StatusUnit
0
0
5
R/W
0x0503
1284
v_MOdE
0
0
1
R/W
0x0504
1285
Active_SetPoint_Environment
0.0
-15.0
158.0
R/W
0x0505
1286
actual_SupplySetPoint
0.0
-15.0
158.0
R/W
0x0506
1287
actual_SupplySetPoint_Heating
0.0
-15.0
158.0
R/W
0x0507
1288
actual_SupplySetPoint_Cooling
0.0
-15.0
158.0
R/W
0x0508
1289
actualSP_Humidification
0
0
100
R/W
0x0509
1290
actualSP_DeHumidification
0
0
100
R/W
0x050A
1291
Status_SupplyFan
0
0
6
0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL,
6=Manual
R/W
0x050B
1292
Status_ReturnFan
0
0
6
0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL,
6=Manual
R/W
0x050C
1293
Status_PumpHeat
0
0
5
R/W
0x050D
1294
Status_PumpCool
0
0
5
R/W
0x050E
1295
Status_Humidifier
0
0
7
0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL,
R/W