0x0652
1619
Pr01_SetPointDiff_HeatRecover
5.0
0.0
36.0
R/W
0x0653
1620
Pr02_Diff_HeatRecover
3.0
0.0
36.0
R/W
0x0654
1621
Pr03_SetPoint_MinTemp_HeatRecover
1.0
-15.0
158.0
R/W
0x0655
1622
Pr04_Diff_MinTemp_HeatRecover
4.0
0.0
36.0
R/W
0x0656
1623
Pr05_TimeByPass_Recover
5
1
99
Minute
R/W
0x0657
1624
Pr07_MinVal_RecoverAO
0.00
0.00
100.00
R/W
0x0658
1625
Pr08_MaxVal_RecoverAO
100.00
0.00
100.00
R/W
0x0659
1626
PP01_PumpRegulation
0
0
1
R/W
0x065A
1627
PP02_SetON_Pump
5.00
1.00
90.00
R/W
0x065B
1628
PP03_SetOFF_Pump
2.00
1.00
90.00
R/W
0x065C
1629
PP04_TimeOFF_Pump
10
1
99
Minute
R/W
0x065D
1630
PA01_En_Alarm_HourFan
1
0
1
R/W
0x065E
1631
PA02_En_Alarm_HourPump
0
0
1
R/W
0x065F
1632
PA04_AlarmProbe_Delay
10
0
240
R/W
0x0660
1633
PA06_ExpansionDelayAlarm
5
0
999
R/W
0x0661
1634
PA20_ResetType_AlarmDirtyRecoverSwitc
h
1
0
1
R/W
0x0662
1635
PA21_AlarmDirtyRecoverSwitch
30
0
999
R/W
0x0663
1636
PA24_ResetType_AlarmAirFilterSwitch
1
0
1
R/W
0x0664
1637
PA25_AlarmAirFilterSwitch_Delay
30
0
999
R/W
0x0665
1638
PA28_AlarmAirFlowSwitchDelay_Reset
30
0
999
R/W
0x0666
1639
PA29_AlarmAirFlowSwitchDelay
5
0
999
R/W
0x0667
1640
PA31_ResetType_AlarmHumidifier
0
0
1
R/W
0x0668
1641
PA32_HumidifierAlarm_Delay
2
0
999
R/W
0x0669
1642
PA35_EnableType_AntiFreezeAlarm
1
0
2
0=DI, 1=Probe
R/W
0x066A
1643
PA36_AlarmAntiFreeze_Delay
5
0
999
R/W
0x066B
1644
PA38_SetPointAntifreeze
2.0
-15.0
158.0
R/W
0x066C
1645
PA39_DiffAntifreeze
3.0
0.0
18.0
R/W
0x066D
1646
PA40_EnableAlarmRTC
1
0
1
R/W
0x066E
1647
PA41_ResetType_AlarmRTC
1
0
1
R/W
0x066F
1648
PH03_MinValueSetPointTemperature
-5.0
-15.0
158.0
R/W
0x0670
1649
PH04_MaxValueSetPointTemperature
40.0
-15.0
158.0
R/W
0x0671
1650
PH05_Enable_OnOffByKey
1
0
1
R/W
0x0672
1651
PH06_EnableChangeMode_KEY
1
0
1
R/W
0x0673
1652
PH07_Enable_OnOffByDI
1
0
1
R/W