EVCO c-pro nano RACK Manuale d'uso
Pagina 79

C-PRO NANO RACK E C-PRO MICRO RACK MANUALE APPLICATIVO
Pagina 79
1723 PH05_En_OnOffByKey
1
0
1
R/W
1724 PH07_En_OnOffByDI
0
0
1
R/W
1725 PH08_En_OnOffByDI_Circuit
0
0
1
R/W
1726 PH09_En_OnOffBySuperv
0
0
1
R/W
1727 PH10_En_OnOffBySuperv_Circuit
0
0
1
R/W
1728 PH11_Modbus_Address
1
1
247
R/W
1729 PH12_Modbus_Baud
3
0
4
1=2400,
2=4800,
3=9600,
4=19200
R/W
1730 PH13_Modbus_Parity
2
0
2
0=None,
1=Odd, 2=Even
R/W
1731 PH14_Modbus_StopBit
0
0
1
0=1 bit, 1=2 bit
R/W
1732 PH15_SetDefault_Par
0
0
1
R/W
1733 PH17_Logic_DI_Alarm
1
0
1
R/W
1734 PH18_Logic_DO_Alarm
0
0
1
R/W
1735 PH19_Logic_DI_Other
0
0
1
R/W
1736 PH23_En_EnvironmentProbe
0
0
1
R/W
1737 PH24_En_ExternalProbe
0
0
1
R/W
1738 PH25_En_OffsetSetPoint_FromDig
0
0
1
R/W
1739 PH26_En_OffsetSetPoint_FromSup
0
0
1
R/W
1740 PH31_RefrigerationType
3
0
6
0=none,
1=R22,
2=R134a,
3=R404A,
4=R407C,
5=R410A,
6=R507
R/W
1741 PH32_Temp_UM
0
0
1
0=°C, 1=°F
R/W
1742 PH33_Press_UM
0
0
1
0=Bar, 1=psi
R/W
1743 PH35_EnSuctionCompensation
0
0
1
R/W
1744 PH36_OffsetSuctionCompensation
0.2
0.1
5.0
Bar
R/W
1745 PH40_Pressure_or_Temperature
0
0
1
R/W
1746 PH43_Select_UniversalAI3
4
2
5
R/W
1747 PH44_Select_UniversalAI4
4
2
5
R/W
1748 PH50_OnlyIcons
0
0
1
R/W
1749 PH51_EnableNumericIcons
1
0
1
R/W
1750 PH52_EnableEvcoIcon
1
0
1
R/W
1751 PG01_CircuitsNumber
1
1
2
R/W
1752 PG02_En_Expansion
0
0
1
R/W
1753 PG03_DifferentCapacitiesCmp
0
0
1
R/W