EVCO c-pro nano RACK Manuale d'uso
Pagina 76

C-PRO NANO RACK E C-PRO MICRO RACK MANUALE APPLICATIVO
Pagina 76
1620 PC24_Cmp_Inverter_Diff_Circuit1
0.5
0.0
290.0
Bar
R/W
1621 PC25_Cmp_Inverter_OffsetSP_Circuit1
0.0
-290.0
290.0
Bar
R/W
1622 PC26_Cmp_Min_Inverter_Circuit1
-
0.00
100.00
%
R/W
1623 PC27_Cmp_Inverter_TSpeedUp_Circuit1
0
0
999
sec
R/W
1624 PC28_Cmp_InverterTime_Circuit1
10
0
999
sec
R/W
1625 PC31_Cmp_OnErrorProbe_Circuit2
1
0
4
R/W
1626 PC32_Cmp_MinSetPoint_Circuit2
0.1
-145.0
625.5
Bar
R/W
1627 PC33_Cmp_MaxSetPoint_Circuit2
2.5
-145.0
625.5
Bar
R/W
1628 PC34_Cmp_RegulationType_Circuit2
1
0
1
0 = Banda
Laterale, 1 =
Zona Neutra
R/W
1629 PC36_Cmp_PI_Ti_Circuit2
600
0
999
sec
R/W
1630 PC37_Cmp_PI_Diff_Circuit2
0.5
0.0
290.0
Bar
R/W
1631 PC38_Cmp_NZ_Zone_Circuit2
0.5
0.0
290.0
Bar
R/W
1632 PC39_Cmp_NZ_DiffOutZone_Circuit2
0.5
0.0
290.0
Bar
R/W
1633 PC40_Cmp_NZ_TOnMin_Circuit2
20
0
999
sec
R/W
1634 PC41_Cmp_NZ_TOnMax_Circuit2
60
0
999
sec
R/W
1635 PC42_Cmp_NZ_TOffMin_Circuit2
10
0
999
sec
R/W
1636 PC43_Cmp_NZ_TOffMax_Circuit2
60
0
999
sec
R/W
1637 PC44_Cmp_Inverter_Diff_Circuit2
0.5
0.0
290.0
Bar
R/W
1638 PC45_Cmp_Inverter_OffsetSP_Circuit2
0.0
-290.0
290.0
Bar
R/W
1639 PC46_Cmp_Min_Inverter_Circuit2
-
0.00
100.00
%
R/W
1640 PC47_Cmp_Inverter_TSpeedUp_Circuit2
0
0
999
sec
R/W
1641 PC48_Cmp_InverterTime_Circuit2
10
0
999
sec
R/W
1642 PC69_RestartTimeout
0
0
999
sec
R/W
1643 PC70_EnablePart
0
0
1
R/W
1644 PC71_SetPressurePartCircuit1
22.0
-145.0
625.5
Bar
R/W
1645 PC72_SetPressurePartCircuit2
22.0
-145.0
625.5
Bar
R/W
1646 PC74_DifftPressurePart
4.0
0.1
10.0
Bar
R/W
1647 PC75_MinTimePart
2
0
999
min
R/W
1648 PC76_PartLimit
50
0
100
%
R/W
1649 PC78_OverloadSteps_Cmp
0
0
100
%
R/W
1650 PC8x_CmpPower[0]
0
0
5000
kW
R/W
1651 PC8x_CmpPower[1]
0
0
5000
kW
R/W
1652 PC8x_CmpPower[2]
0
0
5000
kW
R/W
1653 PC8x_CmpPower[3]
0
0
5000
kW
R/W
1654 PF01_Fan_Rotation_Type
0
0
3
0=FIFO,
1=LIFO,
2=FIFO+Hr,
R/W