1031 EnableSecSP_bySup_Fan_Circuit2
0
0
1
R/W
1281 StatusMachine
0
0
3
0=OFF key,
1=OFF dig,
2=OFF sup,
3=ON
R/W
1282 StatusCircuit1
0
0
6
0=disab,
1=OFF, 2=OFF
dig, 3=OFF
sup, 4=ON,
5=ALL
R/W
1283 Cmp_actualSetPoint_Circuit1
-
-145.0
625.5
Bar
R/W
1284 Fan_actualSetPoint_Circuit1
-
-145.0
625.5
Bar
R/W
1285 CmpInv_actualSet_Circuit1
-
-145.0
625.5
Bar
R/W
1286 FanInv_actualSet_Circuit1
-
-145.0
625.5
Bar
R/W
1287 PowerRequested_Circuit1
0
0
100
%
R/W
1288 PowerSupplied_Circuit1
0
0
100
%
R/W
1289 StatusCircuit2
0
0
6
0=disab,
1=OFF, 2=OFF
dig, 3=OFF
sup, 4=ON,
5=ALL
R/W
1290 Cmp_actualSetPoint_Circuit2
-
-145.0
625.5
Bar
R/W
1291 Fan_actualSetPoint_Circuit2
-
-145.0
625.5
Bar
R/W
1292 CmpInv_actualSet_Circuit2
-
-145.0
625.5
Bar
R/W
1293 FanInv_actualSet_Circuit2
-
-145.0
625.5
Bar
R/W
1294 PowerRequested_Circuit2
0
0
100
%
R/W
1295 PowerSupplied_Circuit2
0
0
100
%
R/W
1537 SPC1_Cmp_SetPoint_Circuit1
1.0
-145.0
625.5
Bar
R/W
1538 PUC1_Cmp_SPOffset_ByDig_Circuit1
0.0
-290.0
290.0
Bar
R/W
1539 PUC4_Cmp_SPOffset_BySup_Circuit1
0.0
-290.0
290.0
Bar
R/W
1540 SPF1_Fan_SetPoint_Circuit1
15.0
-145.0
625.5
Bar
R/W
1541 PUF1_Fan_SPOffset_ByDig_Circuit1
0.0
-290.0
290.0
Bar
R/W
1542 PUF4_Fan_SPOffset_BySup_Circuit1
0.0
-290.0
290.0
Bar
R/W
1543 SPC2_Cmp_SetPoint_Circuit2
1.0
-145.0
625.5
Bar
R/W
1544 PUC2_Cmp_SPOffset_ByDig_Circuit2
0.0
-290.0
290.0
Bar
R/W
1545 PUC5_Cmp_SPOffset_BySup_Circuit2
0.0
-290.0
290.0
Bar
R/W
1546 SPF2_Fan_SetPoint_Circuit2
15.0
-145.0
625.5
Bar
R/W
1547 PUF2_Fan_SPOffset_ByDig_Circuit2
0.0
-290.0
290.0
Bar
R/W
1548 PUF5_Fan_SPOffset_BySup_Circuit2
0.0
-290.0
290.0
Bar
R/W
1549 PM00_ManutHourCmp ( Low )
2000.0
0.0
9999.0
ore x 10
R/W
1550 PM00_ManutHourCmp ( High )