3=LIFO+Hr
1655 PF02_Fan_EnRegulationByCmp
0
0
1
0=CPP_CPP,
1=CC_PPPP
R/W
1656 PF07_Fan_TOnOther
2
0
999
sec
R/W
1657 PF08_Fan_TOffOther
2
0
999
sec
R/W
1658 PF11_Fan_OnErrorProbe_Circuit1
1
0
4
R/W
1659 PF12_Fan_MinSetPoint_Circuit1
1.0
-145.0
625.5
Bar
R/W
1660 PF13_Fan_MaxSetPoint_Circuit1
25.0
-145.0
625.5
Bar
R/W
1661 PF14_Fan_RegulationType_Circuit1
0
0
1
0 = Banda
Laterale, 1 =
Zona Neutra
R/W
1662 PF16_Fan_PI_Ti_Circuit1
600
0
999
sec
R/W
1663 PF17_Fan_PI_Diff_Circuit1
0.5
0.0
290.0
Bar
R/W
1664 PF18_Fan_NZ_Zone_Circuit1
1.0
0.0
290.0
Bar
R/W
1665 PF20_Fan_NZ_TOnOff_Circuit1
10
0
999
Bar
R/W
1666 PF24_Fan_Inverter_Diff_Circuit1
0.5
0.0
290.0
Bar
R/W
1667 PF25_Fan_Inverter_OffsetSP_Circuit1
0.0
-290.0
290.0
Bar
R/W
1668 PF26_Fan_Min_Inverter_Circuit1
-
0.00
100.00
%
R/W
1669 PF27_Fan_Inverter_TSpeedUp_Circuit1
2
0
999
sec
R/W
1670 PF28_Fan_InverterTime_Circuit1
10
0
999
sec
R/W
1671 PF31_Fan_OnErrorProbe_Circuit2
1
0
4
R/W
1672 PF32_Fan_MinSetPoint_Circuit2
1.0
-145.0
625.5
Bar
R/W
1673 PF33_Fan_MaxSetPoint_Circuit2
25.0
-145.0
625.5
Bar
R/W
1674 PF34_Fan_RegulationType_Circuit2
0
0
1
0 = Banda
Laterale, 1 =
Zona Neutra
R/W
1675 PF36_Fan_PI_Ti_Circuit2
600
0
999
sec
R/W
1676 PF37_Fan_PI_Diff_Circuit2
0.5
0.0
290.0
Bar
R/W
1677 PF38_Fan_NZ_Zone_Circuit2
1.0
0.0
290.0
Bar
R/W
1678 PF40_Fan_NZ_TOnOff_Circuit2
10
0
999
sec
R/W
1679 PF44_Fan_Inverter_Diff_Circuit2
0.5
0.0
290.0
Bar
R/W
1680 PF45_Fan_Inverter_OffsetSP_Circuit2
0.0
-290.0
290.0
Bar
R/W
1681 PF46_Fan_Min_Inverter_Circuit2
-
0.00
100.00
%
R/W
1682 PF47_Fan_Inverter_TSpeedUp_Circuit2
2
0
999
sec
R/W
1683 PF48_Fan_InverterTime_Circuit2
10
0
999
sec
R/W
1684 PF71_EnableFloatingCond
0
0
1
R/W
1685 PF72_FloatingCond_Offset
-
-20.0
20.0
°C
R/W
1686 PF73_FloatingCond_SetMin
30.0
10.0
45.0
°C
R/W
1687 PF74_FloatingCond_SetMax
40.0
10.0
45.0
°C
R/W