0x067E 1663 Pb01_Temperature_Diff_Valve
10.0
0.0
36.0
R/W
0x067F 1664 Pb02_Valve_Ti
0
0
999
R/W
0x0680 1665 Pb03_NeutralZone_Temperature
4.0
0.0
36.0
R/W
0x0681 1666 Pb05_Offset_ValveSupplySetPoint
0.0
0.0
36.0
R/W
0x0682 1667 Pb06_Diff_ValveSupplySetPoint
5.0
0.0
36.0
R/W
0x0683 1668 Pb10_ForceHeatValve_OnErrorProbe
30.00
0.00
100.00
R/W
0x0684 1669 Pb11_ForceCoolValve_OnErrorProbe
30.00
0.00
100.00
R/W
0x0685
1670
Pb15_PriorityCoolingReq
0 0 3
R/W
0x0686 1671 Pb20_ResistorOnOffDelayTime
60
0
999
R/W
0x0687 1672 PU02_NeutralZone_Humidity
6
0
100
R/W
0x0688 1673 PU03_Humidity_Diff
10
0
100
R/W
0x0689 1674 PU04_ValveDeHumidification_Ti
0
0
999
R/W
0x068A
1675
PU05_EnLimitDeHumid
0 0 1
R/W
0x068B
1676
PU10_tSupply_EnableHumidifier
1 0 1
R/W
0x068C 1677 PU11_tSupply_EnableHumidifier_Set
22.0
-15.0
158.0
R/W
0x068D 1678 PU12_tSupply_EnableHumidifier_Diff
3.0
0.0
68.0
R/W
0x068E
1679
PU13_hSupply_EnableHumidifier
1 0 1
R/W
0x068F
1680
PU14_hSupply_EnableHumidifier_Set1
80 0 95
R/W
0x0690
1681
PU15_hSupply_EnableHumidifier_Diff1
20 0 40
R/W
0x0691
1682
PS01_Type_FreeCoolingHeating
0 0 1
R/W
0x0693
1684
PS03_Type_ControlShutter
0 0 4
R/W
0x0695 1686 PS05_MinRegulationValue_AirExternalShutter
20.00
0.00
100.00
R/W
0x0696 1687 PS06_MaxRegulationValue_AirExternalShutter
100.00
0.00
100.00
R/W
0x0697 1688 PS07_PreStartTime_extDamper
45
0
65535
R/W
0x0698 1689 PS08_DelayOFF_extDamper
15
0
65535
R/W
0x0699 1690 PS09_FineCorsa_WaitTime
30
0
999
R/W
0x069A 1691 PS10_FixRegulationValue_AirExternalShutter
50.00
0.00
100.00
R/W
0x069B 1692 PS12_FreeCoolingHeatingTemp_enDiff
2.0
0.0
36.0
R/W
0x069C 1693 PS13_FreeCoolingHeatingTemp_enSetPoint
4.0
0.0
68.0
R/W
0x069D
1694
PS15_EnableMinVal_AirExternalShutter
0 0 2
R/W
0x069E 1695 PS20_AirQuality_SetPoint
600
0
10000
R/W
0x069F 1696 PS21_AirQuality_Diff
100
0
2000
R/W
0x06A0 1697 Pr01_SetPointDiff_HeatRecover
5.0
0.0
36.0
R/W
0x06A1 1698 Pr02_Diff_HeatRecover
3.0
0.0
36.0
R/W
0x06A2 1699 Pr03_SetPoint_MinTemp_HeatRecover
1.0
-15.0
158.0
R/W
0x06A3 1700 Pr04_Diff_MinTemp_HeatRecover
4.0
0.0
36.0
R/W
0x06A4 1701 Pr05_TimeByPass_Recover
5
1
99
R/W
0x06A5 1702 Pr07_MinVal_RecoverAO
0.00
0.00
100.00
R/W
0x06A6 1703 Pr08_MaxVal_RecoverAO
100.00
0.00
100.00
R/W
0x06A7
1704
PP01_PumpRegulation
0 0 1
R/W