EVCO EPU2BXP1AH Manuale d'uso
Pagina 93

EVCO S.p.A. c-pro 3 micro AHU/c-pro 3 kilo AHU | Manuale applicativo ver. 1.1 | Code 144CP3UKAHI104
page 93 of 104
0x0286 647 out_Humidifier
0.00
0.00
100.00
R/W
0x0287 648 out_MixDamper
0.00
0.00
100.00
R/W
0x0288 649 out_Recover
0.00
0.00
100.00
R/W
0x0300 769 PackedAlarm_1
0
0
65535
R/W
0x0301 770 PackedAlarm_2
0
0
65535
R/W
0x0400
1025
Status_OnOff_bySUP
0 0 1
R/W
0x0401
1026
Status_MOde_bySUP
0 0 1
R/W
0x0402
1027
Status_En_OffsetSP_bySUP
0 0 1
R/W
0x0500
1281
CLOCK_RTC ( Low )
-
01/01/2000
19/01/2068 03:14:07
R/W
0x0501
1282
CLOCK_RTC ( High )
0x0502 1283 statusUnit
0
0
255
R/W
0x0503
1284
v_MOdE
1 0 1
R/W
0x0504 1285 Active_SetPoint_Environment
0.0
-15.0
158.0
R/W
0x0505 1286 actual_SupplySetPoint
0.0
-15.0
158.0
R/W
0x0506 1287 actual_SupplySetPoint_Heating
0.0
-15.0
158.0
R/W
0x0507 1288 actual_SupplySetPoint_Cooling
0.0
-15.0
158.0
R/W
0x0508 1289 actualSPhum
0
-32768
32767
R/W
0x0509 1290 actualSPdeHhum
0
-32768
32767
R/W
0x050A
1291
Status_SupplyFan
0 0 6
R/W
0x050B
1292
Status_ReturnFan
0 0 6
R/W
0x050C
1293
Status_Pump1
0 0 4
R/W
0x050D
1294
Status_Pump2
0 0 4
R/W
0x050E
1295
Status_Humidifier
0 0 4
R/W
0x050F
1296
Status_Recover
0 0 4
R/W
0x0510
1297
statusHeater1
0 0 5
R/W
0x0511
1298
statusHeater2
0 0 5
R/W
0x0512
1299
Status_extDamper
0 0 5
R/W
0x0513
1300
Status_MixAirShutter
0 0 5
R/W
0x0514 1301 Position_MixShutter
0.00
0.00
100.00
R/W
0x0515 1302 UI_TBactual
0
0
255
R/W
0x0516 1303 TBoffset
0.0
-3276.8
3276.7
R/W
0x0517 1304 limitC
0.00
0.00
100.00
R/W
0x0518 1305 limitH
0.00
0.00
100.00
R/W
0x0519 1306 Request_AirQuality
0.00
0.00
100.00
R/W
0x051A 1307 Req_FreeCoolingHeating
0.00
0.00
100.00
R/W
0x051B 1308 DeHumid_ValveRequest
0.00
0.00
100.00
R/W
0x0600
1537
F1_Monday_p1
0 0 4
R/W
0x0601
1538
F1_Monday_h1 ( Low )
00:00:00
00:00:00
23:59:59
R/W
0x0602
1539
F1_Monday_h1 ( High )
0x0603
1540
F2_Monday_p2
0 0 4
R/W