Fronius Symo x.x-3-S Manuale d'uso
Pagina 59

57
EN
FRONIUS ECO
25.0-3-S
27.5-3-S
Input data
MPP voltage range
580 - 850 V DC
580 - 850 V DC
Max. input voltage
(at 1,000 W/m²/ -10 °C in an open circuit)
1000 V DC
Min. input voltage
580 V DC
Max. input current
44.2 A
47.7 A
Max. short circuit current of the solar modules
(I
SC PV
)
66.3 A
71.6 A
Max. feedback current
4)
48 A (RMS)
5)
Output data
Nominal output power (P
nom
)
25000 W
27000 W
Max. output power
25000 W
27000 W
Nominal grid voltage
3 ~ NPE 220/230 V / 380/400 V
Min. grid voltage
150 V / 260 V
Max. grid voltage
275 V / 477 V
Nominal output current at 220 / 230 V
37.9 / 36.2 A
40.9 / 39.1 A
Max. output current
38 A
41 A
Nominal frequency
50 / 60 Hz
1)
Total harmonic distortion
< 2 %
Power factor cos phi
0 - 1 ind./cap.
2)
Max. output fault current per period
A/ms
General data
Maximum efficiency
98 %
European efficiency U
DCmin
/ U
DCnom
/ U
DCmax
97.99 / 97.47 / 97.07 %
97.98 / 97.59 / 97.19 %
Overnight self-consumption
W & VA
Cooling system
Controlled forced-air ventilation
Degree of protection
IP 66
Dimensions h x w x d
725 x 510 x 225 mm
Weight (light version)
35.69 kg (35.44 kg)
Permissible ambient temperature
-25 °C - +60 °C
Permitted humidity
0 - 100 %
EMC device class
Q
Overvoltage category DC / AC
2 / 3
Pollution level
2
Noise emission
dB(A) (ref. 1pW)
Protection devices
DC insulation measurement
Integrated
Response to DC overload
Operating point shift, power limitation
DC disconnector
Integrated
DC overvoltage protection
Integrated
RCMU
Integrated