Class 3 status
codes
Class 3 includes status codes that may occur while feeding energy into the grid, but gen-
erally do not cause the process to be interrupted for any length of time.
The inverter disconnects automatically from the grid, the grid is then monitored as specified
and the inverter attempts to resume feeding energy into the grid.
*) If the status code is displayed all the time: notify a Fronius-trained service engineer
**) Fault is rectified automatically. If this status code keeps recurring, contact your system
engineer
Code
Description
Behaviour
Remedy
301
Overcurrent (AC)
Short-term interruption while
feeding energy into the grid.
The inverter resumes its start-
up routine.
*)
302
Overcurrent (DC)
303
DC module overtemperature
Short-term interruption while
feeding energy into the grid.
The inverter resumes with its
startup routine.
Purge cooling air open-
ings and heat sink; **)
304
AC module overtemperature
305
No power being fed in, despite closed
relay
Short-term interruption while
feeding energy into the grid.
The inverter resumes with its
startup routine.
**)
306
PV output too low for feeding energy
into the grid
Short-term interruption while
feeding energy into the grid
The inverter resumes its start-
up routine.
wait for sufficient level of
insolation;
**)
307
DC low
DC input voltage too low for feeding
energy into the grid
IMPORTANT! Due to the low level of insolation early in the morning and in the evening, the status codes 306
(Power low) and 307 (DC low) are displayed routinely at these times of day. These status codes do not indicate
any kind of fault.
308
Intermediate circuit voltage too high
Short-term interruption while
feeding energy into the grid
The inverter resumes its start-
up routine.
**)
309
DC input voltage MPPT 1 too high
311
Polarity of DC strings reversed
313
DC input voltage MPPT2 too high
314
Current sensor calibration timeout
Short-term interruption while
feeding energy into the grid.
The inverter resumes with its
startup routine.
*)
315
AC current sensor error
316
InterruptCheck fail
325
Overtemperature in the connection
area
326
Fan 1 error
327
Fan 2 error