8

Heat pump
control unit

1) Use a 30 mm hexagonal

wrench to unscrew the plug

on the pocket that has been

fitted for installation of the

flow switch.

2) Position the flow switch in accordance with the flow direction

indicated on the upper part of the switch, place the seal in

position and tighten the nut until it is watertight. When inserting

inside the pocket, be careful with the flow switch actuation

blade and the direction it is secured in: the blade must be

absolutely perpendicular to the flow direction.

Installation of optional components

A) 315 series flow switch
If the heat pump needs to be connected to a flow switch, this

control device can be installed as shown in the figure.

Wiring diagrams

In a geothermal installation, the flow switch must be connected to

the heat pump control unit, which is usually prefitted for this

connection.

N.B. Check the current absorbed by the utility that the flow switch

is connected to. If this value is greater than 0,02 A, a relay
must be installed between the flow switch and the user

device itself to prevent damage to the flow switch contacts.

Heat pump
control unit

1) Use a 16 mm hexagonal

wrench to unscrew the plug

on the pocket that has been

fitted for connection to the

pressure switch.

2) Install the pressure

switch,

with

the

cable

fairleads

facing

the

ball

valves.

B) 625 series safety pressure switch
The 625 series safety pressure switch can be installed as shown.

Wiring diagrams

1) Make the electrical connections.

In a geothermal installation, the minimum pressure safety switch

must be connected to the heat pump control unit, which is usually

prefitted for this connection.

2) Use a screw driver or pointed

object to press the reset

switch on the pressure switch

and make it ready.