Geothermal probes – Caleffi 115 Manuale d'uso
Pagina 16

4
2) Position the manifold at right angles to the heat pump. The
heat pump line must be connected to the manifold ball valves.
The direction of flow is indicated on the manifold labels.
3) The manifold, supplied with heat pump pipe fittings on the right,
is reversible and can be positioned with heat pump connection
on the left (see “reversible manifold”).
4) Connect (watertight) the main pipe from the heat pump to the
ball valve with a 1 1/4” F connection.
5) Connect (watertight) the main pipes from the geothermal probes
to the manifold with a 1 1/4” F connection.
6) Reclose the insulation and reinsert the temperature gauges in
their pockets.
7) Set up the drain to fit the safety relief valve. The safety relief
valve discharge pipe must not obstruct normal valve operation
and must not endanger people or things.
In accordance with applicable regulations, the safety relief valve
drain must be visible and conveyed to a collection tray using
suitable pipes.
INSTALLATION IN A GEOTHERMAL PROBE SYSTEM
1) Remove the temperature gauges and discharge tundish, then
the front of the upper insulation. To open the lower insulation,
turn it downwards: it won’t come off until the manifold has been
removed. The insulation is attached with velcro strips. This
system makes it easier to open the insulation.
GEOTHERMAL
PROBES
9) Make the electric connections to the pressure safety switch.
8) Connect the earth cable to the pin on the anchoring plate.