Xylem Q 2Rils 485 Signal delivery panel EN 12845 Manuale d'uso

Pagina 38

Advertising
background image

38

23

Controller fault

18

18

Minimum fuel

level

8

Float switch

See float switch

*

Minimum level of

priming tank

2

*

10

* Identify the terminals from the device diagram. In case of alarm, the final contact must be NO.
N.B.:
1) If the priming tank minimum level alarm signal is not used, jumper terminals 2-10 on terminal block XC2 (KL2) in the
Q-2Rils485 panel.

9.3.3 Diesel unit 2 electrical connections

DIESEL UNIT 2

Unit

Terminal board

Terminal

Description

Terminal

Terminal

board

Panel

DIESEL UNIT 2 PANEL

See manager

25

Common

2

XC2

KL3

Q-2Rils 485

20

Switch not

automatic

12

21

Failure to start

14

22

Pump running

16

23

Controller fault

18

18

Minimum fuel

level

8

Float switch

See float switch

*

Minimum level of

priming tank

2

*

10

* Identify the terminals from the device diagram. In case of alarm, the final contact must be NO.
N.B.:
1) If the priming tank minimum level alarm signal is not used, jumper terminals 2-10 of terminal block XC2 (KL3) of the

Q-2Rils485 panel.

9.3.4 Electrical connections of the auxiliary services: valves, jockey pump, drain pump (if present)

VALVE MONITORING

Unit

Terminal board

Terminal

Description

Terminal

Terminal

board

Panel

“Micro-valve”

position switch

See valve switch

21

Flowmeter valve

1

XC2

KL3

Q-2Rils 485

22

22

13

Pump 1 suction

valve

1

XC2

KL2

Q-2Rils 485

14

4

13

Pump 1 delivery

side valve

1

14

6

13

Pump 2 suction

valve

1

XC2

KL3

Q-2Rils 485

14

4

13

Pump 2 delivery

side valve

1

14

6

Advertising