Xylem Q 2Rils 485 Signal delivery panel EN 12845 Manuale d'uso
Pagina 33

33
9.1 SETS with: one ELECTRIC PUMP and one DIESEL UNIT.
Typology of compatible sets: (GEN..10D, GEN..11D) and auxiliary services (if present).
9.1.1 Position of micro-switches
Unit code
Unit
Micro-switch
Micro-switch configuration
GEN..10D
GEN..11D
KL2
Q2Rils485
SW1
Position
1
2
ON
ON
SW2
Position
1
2
3
ON
OFF
ON
SW3
Position
1
2
3
4..10
ON
OFF
OFF
-
KL3
Q2Rils485
SW1
Position
1
2
ON
ON
SW2
Position
1
2
3
OFF
ON
ON
SW3
Position
1
2
3
4..10
OFF
ON
OFF
-
9.1.2 Electric pump connections
ELECTRIC PUMP
Unit
Terminal board
Terminal
Description
Terminal
Terminal
board
Unit
ELECTRIC PUMP
PANEL
See panel
7
Common
2
XC2
KL2
Q-2Rils 485
8
Incorrect phase
sequence
12
9
Pump on demand
14
10
Pump running
16
11
Failure to start
18
Float switch
see float switch
*
Minimum level of
suction tank
2
*
8
Float switch
see float switch
*
Minimum level of
priming tank
2
*
10
* Identify the terminals from the device diagram. In case of alarm, the final contact must be NO.