Xylem Q 2Rils 485 Signal delivery panel EN 12845 Manuale d'uso
Pagina 35

35
JOCKEY PUMP
Unit
Terminal board
Terminal
Description
Terminal
Terminal
board
Panel
JOCKEY PUMP PANEL
Relay KA1
11
Jockey pump
running
2
XC2
KL2
Q-2Rils 485
14
20
Relay KA2
11
Overload
2
14
22
Important: The jockey pump panel, if present, must be version CP with clean contacts.
1) If the jockey pump running signal is not used, jumper terminals 2-20 on terminal block XC2 (KL2) in the Q-2Rils 485
panel or do not enable monitoring from QAL 12845.
DRAIN PUMP
Unit
Terminal board
Terminal
Description
Terminal
Terminal
board
Panel
DRAIN PUMP PANEL
See panel
**
Overload
2
XC2
KL3
Q-2Rils 485
**
20
**) Identify the terminals from the device diagram. In case of alarm, the final contact must be NO.
9.2 SETS with one ELECTRIC PUMP
Typology of compatible sets: (GEN..10, GEN..11) and auxiliary services (if present).
9.2.1 Position of micro-switches
Set code
Unit
Micro-switch
Micro-switch configuration
GEN..10
GEN..11
KL2
Q2Rils485
SW1
Position
1
2
ON
ON
SW2
Position
1
2
3
ON
OFF
OFF
SW3
Position
1
2
3
4..10
ON
OFF
OFF
-
KL3
Q2Rils485
SW1
Position
1
2
ON
ON
SW2
Position
1
2
3
OFF
OFF
ON
SW3
Position
1
2
3
4..10
OFF
ON
OFF
-