Xylem Q 2Rils 485 Signal delivery panel EN 12845 Manuale d'uso
Pagina 37

37
1) If the jockey pump running signal is not used, jumper terminals 2-4 on terminal block XC2 (KL3) in the Q-2Rils 485
panel or do not enable monitoring from QAL 12845.
DRAIN PUMP
Unit
Terminal board
Terminal
Description
Terminal
Terminal
board
Panel
DRAIN PUMP PANEL
See panel
**
Overload
2
XC2
KL3
Q-2Rils 485
**
8
**) Identify the terminals from the device diagram. In case of alarm, the final contact must be NO.
9.3 SETS with TWO DIESEL UNITS.
Typology of compatible sets: GEN..00D2, GEN..01D2 and auxiliary services (if present).
9.3.1 Position of micro-switches
Set code
Unit
Micro-switch
Micro-switch configuration
GEN..00D2,
GEN..01D2
KL2
Q2Rils485
SW1
Position
1
2
ON
ON
SW2
Position
1
2
3
OFF
ON
ON
SW3
Position
1
2
3
4..10
ON
OFF
OFF
-
KL3
Q2Rils485
SW1
Position
1
2
ON
ON
SW2
Position
1
2
3
OFF
ON
ON
SW3
Position
1
2
3
4..10
OFF
ON
OFF
-
9.3.2 Diesel unit 1 electrical connections
DIESEL UNIT 1
Unit
Terminal board
Terminal
Description
Terminal
Terminal
board
Panel
DIESEL UNIT 1 PANEL
See panel
25
Common
2
XC2
KL2
Q-2Rils 485
20
Switch not
automatic
12
21
Failure to start
14
22
Pump running
16