EVCO EPU2LXP1CH Manuale d'uso
C-pro 3 micro+ and c-pro 3 kilo, Programmable controllers

EVCO S.p.A. • Code 104CP3KPE113 • page 1/2
c-pro 3 micro+ and c-pro 3 kilo+
Programmable controllers
version 1.1
4.3
Additional information for installation
• working conditions (working temperature, humidity, etc.) must be be-
tween the limits indicated in the technical data
• do not install the controller close to heating sources (heaters, hot air
ducts, etc.), devices provided with big magnetos (big speakers, etc.),
locations subject to direct sunlight, rain, humidity, dust, mechanical
vibrations or bumps
• according to the safety legislation, the protection against electrical
parts must be ensured by a correct installation of the controller; the
parts that ensure the protection must be installed so that you can not
remove them if not by using a tool.
5
ELECTRICAL CONNECTION
5.1
Electrical connection models with 9 electrome-
chanical relays
5.2
Electrical connection models with 7 electrome-
chanical relays and 2 solid state relays
5.3
Electrical connection models with 7 electrome-
chanical relays and unipolar stepper electronic
expansion valves driver
5.4
Meaning of connectors
The following tables show the meaning of the connectors.
DIGITAL OUTPUTS
Digital outputs 6 and 7 (electromechanical relays).
TERM. MEANING
NO6
normally open contact digital output 6
NO7
normally open contact digital output 7
CO6/7 common digital outputs 6 and 7
Digital outputs 1... 5 (electromechanical relays).
TERM. MEANING
NO1
normally open contact digital output 1
NO2
normally open contact digital output 2
CO1/2 common digital outputs 1 and 2
NO3
normally open contact digital output 3
NO4
normally open contact digital output 4
NO5
normally open contact digital output 5
CO3/4/5 common digital outputs 3, 4 and 5
GB
ENGLISH
1
GETTING STARTED
1.1
Important
Read these instructions carefully before installing and using the control-
ler and follow all additional information for installation and electrical
connection; keep these instructions close to the controller for future
consultations.
The controller must be disposed according to the local
legislation about the collection for electrical and electronic
equipment.
2
INTRODUCTION
2.1
Introduction
c-pro 3 micro+ and c-pro 3 kilo+ are two families of programmable
controllers.
The families are available in the version:
• with 128 x 64 pixel single colour LCD graphic display (black with
rearlighting through white LED) and with a 6 buttons (with preset
functions) keyboard made of silicone rubber integrated in the control-
ler, hereinafter also called built-in LCD versions (not available in
c-pro 3 micro+)
• with 4 + 4 digit custom display (with function icons) and with a 6
buttons (with preset functions) keyboard made of silicone rubber inte-
grated in the controller, hereinafter also called built-in LED versions
• blind (usable for example with an user interface such as
Vgraph,
Vtouch, Vroom or Vcolor) hereinafter also called blind versions.
The controllers have got:
- real time clock
- 9 analog inputs of which 6 configurable via configuration parameter
for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V ratiometric
/ 0-10 V transducers and 3 configurable via configuration parameter
for PTC / NTC / Pt 1000 probes
- 9 optoisolated digital inputs at 24 VAC / DC of which 7 at 50 / 60 Hz
and 2 up to 2 KHz
- 6 non optoisolated analog outputs of which 2 configurable via con-
figuration parameter for PWM / 0-10 V signal, 2 configurable via con-
figuration parameter for 0-20 mA / 4-20 mA / 0-10 V signal and 2 for
0-10 V signal
- according to the model:
• 9 digital outputs (electromechanical relays) of which seven
3 res. A @ 250 VAC SPST outputs and two 3 res. A @ 250 VAC SPDT
outputs
• 9 digital outputs of which seven 3 res. A @ 250 VAC SPST electrome-
chanical relays and two solid stare relays (24 VAC/DC, 0.6 A max.)
• seven 3 res. A @ 250 VAC SPST digital outputs (electromechanical re-
lays) and an unipolar stepper electronic expansion valves driver
- 4 non optoisolated communication ports of which 1 USB OTG port
(for programming and debugging), 1 CAN port with CANbus com-
munication protocol, 1 RS-485 port with Modbus master communica-
tion protocol and 1 RS-485 port with Modbus slave communication
protocol.
Through the I/O expansion
c-pro 3 EXP micro+ or c-pro 3 EXP kilo+ it
is possible to increase the number of inputs and outputs.
Through the development environment UNI-PRO 3 (to order separately)
it is possible to realize the application software and through the con-
necting cable 0810500018 (2 m, 6,561 ft long) or 0810500020 (0.5 m,
1.640 ft long), to order separately, it is possible to program the control-
ler.
The devices look in case 4 DIN modules.
Installation is in electrical panel, on DIN rail.
Through a common USB peripheral it is possible to make the upload
and the download of the configuration parameters.
For further information please consult the
Hardware manual of
c-pro 3.
3
DESCRIPTION
3.1
Description
The following table shows the meaning of the parts of the controller.
PART
MEANING
1
digital outputs 6 and 7
2
digital outputs 1... 5
3
according to the model:
- digital output 9
- unipolar stepper electronic expansion valves driver
4
display and keyboard (not available in the blind versions)
5
analog inputs 7... 9, digital inputs 6... 9 and analog outputs
4... 6
6
analog inputs 1... 6, digital inputs 1... 5 and analog outputs
1... 3
7
USB OTG port
8
micro-switch to:
- plug in the termination of the RS-485 port with Modbus
slave communication protocol
- plug in the termination of the CAN port
9
power supply, RS-485 port with Modbus slave communica-
tion protocol and CAN port
10
RS-485 port with Modbus master communication protocol
11
micro-switch to plug in the termination of the RS-485 port
with Modbus master communication protocol
12
signalling LEDs
13
according to the model:
- digital output 8
- unipolar stepper electronic expansion valves driver
4
SIZE AND INSTALLATION
4.1
Size
4 DIN modules; size in mm (in).
4.2
Installation
On DIN rail 35.0 x 7.5 mm (1.377 x 0.295 in) or 35.0 x 15.0 mm
(1.377 x 0.590 in).
To install
c-pro 3 micro+ and c-pro 3 kilo+ operate as shown in the
following drawing.
To remove
c-pro 3 micro+ and c-pro 3 kilo+ remove possible extract-
able screw terminal blocks plugged at the bottom first, then operate on
the DIN rail clips with a screwdriver as shown in the following drawing.
To install
c-pro 3 micro+ and c-pro 3 kilo+ again press the DIN rail clips
to the end first.
DIGITAL OUTPUTS
Digital output 8 (if present, according to the model, electromechanical
relay or solid state relay).
TERM. MEANING
CO8
common digital output 8
NO8
normally open contact digital output 8
NC8
normally open contact digital output 8
DIGITAL OUTPUTS
Digital output 9 (if present, according to the model, electromechanical
relay or solid state relay).
TERM. MEANING
CO9
common digital output 9
NO9
normally open contact digital output 9
NC9
normally open contact digital output 9
UNIPOLAR EEV VALVE
Unipolar stepper electronic expansion valves driver (if present).
TERM. MEANING
SOA
unipolar stepper motor coli 1
SOB
unipolar stepper motor coli 2
SOC
unipolar stepper motor coli 3
SOD
unipolar stepper motor coli 4
COM12V motor power supply (12 VDC, 260 mA max.)
RS485
RS-485 port with Modbus master communication protocol (with net-
work already polarized internally).
TERM. MEANING
GND
ground
A / +
terminal 1 of the transceiver
B / -
terminal 0 of the transceiver
RS485 LT
Micro-switch to plug in the termination of the RS-485 port with Modbus
master communication protocol.
Position micro-switch 1 on position ON to plug in the termination of the
RS-485 port.
Analog inputs 7... 9, digital inputs 6... 9 and analog outputs 4... 6.
TERM. MEANING
GND
common analog inputs and analog outputs
AI7
analog input 7 (configurable via configuration parameter
for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V
ratiometric / 0-10 V transducers)
AI8
analog input 8 (configurable via configuration parameter
for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V
ratiometric / 0-10 V transducers)
AI9
analog input 9 (configurable via configuration parameter
for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V
ratiometric / 0-10 V transducers)
AO4
analog output 4 (configurable via configuration parameter
for 0-20 mA / 4-20 mA / 0-10 V signal)
AO5
analog output 5 (for 0-10 V signal)
AO6
analog output 6 (for 0-10 V signal)
DI6
digital input 6 (optoisolated, at 24 VAC / DC and at
50 / 60 Hz)
DI7
digital input 7 (optoisolated, at 24 VAC / DC and at
50 / 60 Hz)
DI8
digital input 8 (optoisolated, at 24 VAC / DC and at
50 / 60 Hz)
DI9
digital input 9 (optoisolated, at 24 VAC / DC and at
50 / 60 Hz)
COM
common digital inputs
Power supply, RS-485 port with Modbus slave communication protocol,
CAN port.
TERM. MEANING
V≅+
power supply controller (12 VAC in
c-pro 3 micro+,
24 VAC / 20... 30 VDC in
c-pro 3 kilo+); connect the phase
V≅-
power supply controller (12 VAC in
c-pro 3 micro+,
24 VAC / 20... 30 VDC in
c-pro 3 kilo+); connect the neu-
tral
A / +
terminal 1 of the transceiver RS-485 port
B / -
terminal 0 of the transceiver RS-485 port
CAN + signal + CAN port
CAN -
signal - CAN port
If the controller is supplied in direct current, it will be necessary to re-
spect the polarity of the power supply voltage.
CAN LT
Micro-switch to plug in the termination of the CAN port.
Position micro-switch 2 on position ON to plug in the termination of the
CAN port.
RS485 LT
Micro-switch to plug in the termination of the RS-485 port with Modbus
slave communication protocol.
Position micro-switch 1 on position ON to plug in the termination of the
RS-485 port.
USB
USB OTG port.
Analog inputs 1... 6, digital inputs 1... 5 and analog outputs 1... 3.
TERM. MEANING
AI1
analog input 1 (configurable via configuration parameter
for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V
ratiometric / 0-10 V transducers)
AI2
analog input 2 (configurable via configuration parameter
for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V
ratiometric / 0-10 V transducers)
AI3
analog input 3 (configurable via configuration parameter
for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V
ratiometric / 0-10 V transducers)
AI4
analog input 4 (configurable via configuration parameter
for PTC / NTC / Pt 1000 probes)
AI5
analog input 5 (configurable via configuration parameter
for PTC / NTC / Pt 1000 probes)
AI6
analog input 6 (configurable via configuration parameter
for PTC / NTC / Pt 1000 probes)
DI4
digital input 4 (optoisolated, at 24 VAC / DC and up to 2
KHz)
DI5
digital input 5 (optoisolated, at 24 VAC / DC and up to 2
KHz)
COM
common digital inputs
+12V
power supply 0-20 mA / 4-20 mA / 0-10 V transducers
(12 VDC, 120 mA max.)
5VS
power supply 0-5 V ratiometric transducers (5 VDC,
60 mA max.)
GND
common analog inputs and analog outputs
AO1
analog output 1 (configurable via configuration parameter
for PWM / 0-10 V signal)
AO2
analog output 2 (configurable via configuration parameter
for PWM / 0-10 V signal)
AO3
analog output 3 (configurable via configuration parameter
for 0-20 mA / 4-20 mA / 0-10 V signal)
DI1
digital input 1 (optoisolated, at 24 VAC / DC and at
50 / 60 Hz)
DI2
digital input 2 (optoisolated, at 24 VAC / DC and at
50 / 60 Hz)
DI3
digital input 3 (optoisolated, at 24 VAC / DC and at
50 / 60 Hz)
5.5
Additional information for electrical connection
• do not operate on the terminal blocks with electrical or pneumatic
screwers
• if the controller has been moved from a cold location to a warm one,
the humidity could condense on the inside; wait about an hour be-
fore supplying it
• test the working power supply voltage, working electrical frequency
and working electrical power of the controller; they must correspond
with the local power supply
• connect the controller to the other devices using a twisted pair
• disconnect the local power supply before servicing the controller
• do not use the controller as safety device
• for repairs and information on the controller please contact EVCO
sales network.
6
SIGNALS
6.1
LEDs at the front of the controller
LED
MEANING
ON
LED power supply
if it is lit, the controller will be supplied
if it is out, the controller will not be supplied
RUN
LED run
if it is lit, the application software will be compiled and run-
ning in release modality
if it flashes slowly, the application software will be compiled
and running in debug modality
if it flashes quickly, the application software will be compiled,
running in debug modality and stopped in a breakpoint
if it is out:
- the controller will not be compatible with the application
software
- the controller will not be enabled to work with the special
ABL (Application Block Libraries)
LED system alarm
if it is lit, an alarm system not resettable via software will be
running
if it flashes slowly, a system alarm with automatic reset will
be running
if it flashes quickly, a system alarm with manual reset will be
running
if it is out, no alarm system will be running
CAN
LED CANbus communication
if it is lit, the controller will be configured to communicate
via CANbus with another device but the CAN communica-
tion will not have been set up
if it flashes slowly, the CANbus communication will have been
set up but it will not be completely correct
if it flashes quickly, the CANbus communication will have
been set up and will be correct
if it is out, no CANbus communication will be running
L1
LED auxiliary
The operation of this LED can be programmed through the
development environment UNI-PRO 3
7
TECHNICAL DATA
7.1
Technical data
Purpose of control: programmable controller for applications in re-
frigeration, ventilation and air conditioning.
Construction of control: electronic control device to be incorpo-
rated.
Box: self-extinguishing grey.
Size: 71.0 x 135.0 x 60.0 mm (2.795 x 5.314 x 2.362 in); 4 DIN mod-
ules.
Size refers to the controller with all the connectors properly plugged.
Installation: on DIN rail 35.0 x 7.5 mm (1.377 x 0.295 in) or
35.0 x 15.0 mm (1.377 x 0.590 in).
Index of protection: IP20; IP40 the front.
Connections: male Micro-Fit connectors (power supply, inputs, ana-
log outputs, CAN port and RS-485 ports) in
c-pro 3 micro+, male ex-
tractable spring terminal blocks pitch 3.5 mm (0.137 in; power supply,
inputs, analog outputs, CAN port and RS-485 ports) for conductors up
to 1.5 mm² (0.0028 in²) in
c-pro 3 kilo+, male JST connectors (unipolar
stepper electronic expansion valves driver), male extractable screw ter-
minal blocks pitch 5.0 mm (0.196 in; digital outputs) for conductors up
to 2.5 mm² (0.0038 in²) and pitch 3.5 mm (0.137 in; unipolar stepper
electronic expansion valves driver), “A” type USB connector (USB port).
The maximum lengths of the connecting cables are the followings:
• power supply controller: 100 m (328 ft)
• analog inputs: 100 m (328 ft); use a shielded cable for:
- analog inputs 7, 8 and 9
- the remaining inputs if configured for PTC or Pt 1000 probes
in case of lengths over or equal to 10 m (32.8 ft)
• power supply transducers: 100 m (328 ft)
• digital inputs: 100 m (328 ft)
• PWM analog output: 1 m (3.280 ft)
• 0-20 mA / 4-20 mA / 0-10 V analog outputs: 100 m (328 ft)
• digital outputs (electromechanical relays): 100 m (328 ft)
• digital outputs (solid state relays): 100 m (328 ft)
• unipolar stepper electronic expansion valves driver: 3 m (9.842 ft)
• RS-485 port: 1,000 m (3,280 ft); also look at the
Modbus specifications
and implementation guides manual
• CAN port:
- 1,000 m (3,280 ft) with baud rate 20,000 baud
- 500 m (1,640 ft) with baud rate 50,000 baud
- 250 m (820 ft) with baud rate 125,000 baud
- 50 m (164 ft) with baud rate 500,000 baud.
One suggests using the connecting kit CJAV18 (female extractable screw
terminal blocks pitch 5.0 mm, 0.196 in; to order separately), the con-
necting kit CJAV19 (wired female Micro-Fit connectors for
c-pro 3 mi-
cro+, to order separately) and the connecting kit CJAV20 (female ex-
tractable spring terminal blocks pitch 3.5 mm (0.137 in) for
c-pro 3
kilo+, to order separately).
To program the controller one suggests to use the connecting cable
0810500018 (2 m, 6 ft long) or 0810500020 (0.5 m, 1.640 ft long), to
order separately.