Se il parametro CFG è impostato a 3 o 4, il secondo setpoint di lavoro
non sarà disponibile.
4.3 Impostazione dei parametri di configurazione
Per accedere alla procedura:
• assicurarsi che non sia in corso alcuna procedura
• premere
e
per 4 s: il display visualizzerà “PA”
• premere
• premere
o
entro 15 s per impostare “-19”
• premere
o non operare per 15 s
• premere
e
per 4 s: il display visualizzerà “SP1”.
Per selezionare un parametro:
• premere
o
Per modificare un parametro:
• premere
• premere
o
entro 15 s
• premere
o non operare per 15 s.
Per uscire dalla procedura:
• premere
e
per 4 s o non operare per 60 s.
Interrompere l'alimentazione dello strumento dopo la mo-
difica dei parametri.
4.4 Ripristino del valore di default dei parametri di confi-
gurazione
• assicurarsi che non sia in corso alcuna procedura
• premere
e
per 4 s: il display visualizzerà “PA”
• premere
• premere
o
entro 15 s per impostare “743”
• premere
o non operare per 15 s
• premere
e
per 4 s: il display visualizzerà “dEF”
• premere
• premere
o
entro 15 s per impostare “149”
• premere
o non operare per 15 s: il display visualizzerà “dEF” lam-
peggiante per 4 s, dopodichè lo strumento uscirà dalla
procedura
• interrompere l'alimentazione dello strumento.
Accertarsi che il valore di default dei parametri sia oppor-
tuno, in particolare se le sonde non sono termocoppie J.
5
SEGNALAZIONI
5.1 Segnalazioni
LED
SIGNIFICATO
out 1 LED carico 1
se è acceso, il carico 1 sarà acceso
se lampeggia:
• sarà in corso la modifica del primo setpoint di lavoro
• sarà in corso una protezione del carico 1 (parametri C1 e
C2)
out 2 LED carico 2
se è acceso, il carico 2 sarà acceso
se lampeggia:
• sarà in corso la modifica del secondo setpoint di lavoro
• sarà in corso una protezione del carico 2 (parametri C7 e
C8)
LED allarme
se è acceso, sarà in corso un allarme
°
C
LED grado Celsius
se è acceso, l’unità di misura delle temperature sarà il grado
Celsius (parametro P2)
°
F
LED grado Fahrenheit
se è acceso, l’unità di misura delle temperature sarà il grado
Fahrenheit (parametro P2)
CODICE SIGNIFICATO
Loc
la tastiera e/o i setpoint di lavoro sono bloccati (parametri r3
e/o r9); si veda il paragrafo 2.4
6
ALLARMI
6.1 Allarmi
CODICE SIGNIFICATO
AL1
Primo allarme di temperatura
Rimedi:
• verificare la temperatura dell’ambiente
• si vedano i parametri A1 e A3
Conseguenze:
• l’uscita di allarme verrà accesa
AL2
Secondo allarme di temperatura
Rimedi:
• verificare la temperatura dell’ambiente
• si vedano i parametri A5 e A7
Conseguenze:
• l’uscita di allarme verrà accesa
iA
Allarme ingresso multifunzione
Rimedi:
• verificare le cause che hanno provocato l’attivazione del-
l’ingresso
• si vedano i parametri i1 e i5
Conseguenze:
• se il parametro i5 è impostato a 1, l’uscita di allarme verrà
accesa
• se il parametro i5 è impostato a 2, i carichi verranno spenti
e l’uscita di allarme verrà accesa
Quando la causa che ha provocato l’allarme scompare, lo strumento
ripristina il normale funzionamento.
7
DIAGNOSTICA INTERNA
7.1 Diagnostica interna
CODICE SIGNIFICATO
Pr1
Errore sonda ambiente
Rimedi:
• si veda il parametro P0
• verificare l’integrità della sonda
• verificare il collegamento strumento-sonda
• verificare la temperatura dell’ambiente
Conseguenze:
• l’attività del carico 1 dipenderà dal parametro C6
• l’attività del carico 2 dipenderà dal parametro C10
• l’uscita di allarme verrà accesa
Quando la causa che ha provocato l’allarme scompare, lo strumento
ripristina il normale funzionamento.
8
DATI TECNICI
8.1 Dati tecnici
Contenitore: autoestinguente grigio.
Grado di protezione del frontale: IP 65.
Connessioni (usare solo conduttori in rame): morsettiere a vite
(alimentazione, ingressi e uscite), connettore a 6 poli (porta seriale; su
richiesta); morsettiere estraibili a molla (alimentazione, ingressi e uscite)
su richiesta.
Temperatura di impiego: da 0 a 55 °C (10 ... 90% di umidità relati-
va senza condensa).
Alimentazione: 230 VCA, 50/60 Hz, 3 VA (approssimativi); 115 VCA
o 12-24 VCA/CC o 12 VCA/CC su richiesta.
Classe di isolamento: 2.
Buzzer di allarme: su richiesta.
Ingressi di misura EVK403J: 1 (sonda ambiente) per termocoppie
J/K.
Ingressi di misura EVK403M: 1 (sonda ambiente) per sonde
PTC/NTC, termocoppie J/K, sonde Pt 100, Pt 1000 e Ni 120 2/3 fili,
trasduttori 0-20/4-20 mA e 0-10/2-10 V (ingresso di misura universale).
Ingressi digitali: 1 (multifunzione) per contatto NA/NC (contatto pu-
lito, 5 V 1 mA).
Campo di misura: da -50 a 150 °C per sonda PTC, da -40 a 110 °C
per sonda NTC, da -100 a 800 °C per termocoppia J, da -100 a
1.300 °C per termocoppia K, da -200 a 650 °C per sonda Pt 100 2/3 fili,
da -200 a 650 °C per sonda Pt 1000 2/3 fili, da -80 a 300 °C per sonda
Ni 120 2/3 fili.
Risoluzione: 0,1 °C/1 °C/1 °F.
Uscite digitali: 3 relè:
• relè carico 1: 16 A res. @ 250 VCA, 5 FLA, 30 LRA
(contatto in scambio)
• relè carico 2: 8 A res. @ 250 VCA, 2 FLA, 12 LRA
(contatto in scambio)
• relè allarme: 8 A res. @ 250 VCA, 2 FLA, 12 LRA
(contatto in scambio).
La corrente massima consentita sul carico 1 è di 10 A.
Porta seriale: porta per la comunicazione con il sistema di supervisione
(attraverso un’interfaccia seriale, via TTL, con protocollo di comunicazio-
ne MODBUS) o con la chiave di programmazione; su richiesta.
GB ENGLISH
9
WORKING SETPOINTS AND CONFIGURATION PARAMETERS
9.1 Working setpoints
MIN.
MAX.
U.M.
DEF.
WORKING SETPOINTS
r1
r2
°C/°F (1) 0.0
first working setpoint
r7
r8
°C/°F (1) 0.0
second working setpoint
9.2 Configuration parameters
PARAM. MIN.
MAX.
U.M.
DEF.
WORKING SETPOINTS
SP1
r1
r2
°C/°F (1) 0.0
first working setpoint
SP2
r7
r8
°C/°F (1) 0.0
second working setpoint
PARAM. MIN.
MAX.
U.M.
DEF.
MEASURE INPUTS (2)
CA1
-25.0
25.0
°C/°F (1) 0.0
room probe offset
P0
0
13
- - -
2
kind of probe
0 = PTC
1 = NTC
2 = J
3 = K
4 = 3 wires Pt 100
5 = 2 wires Pt 100
6 = 3 wires Pt 1000
7 = 2 wires Pt 1000
8 = 4-20 mA
I ITALIANO
9
SETPOINT DI LAVORO E PARAMETRI
DI CONFIGURAZIONE
9.1 Setpoint di lavoro
SETPOINT DI LAVORO
primo setpoint di lavoro
secondo setpoint di lavoro
9.2 Parametri di configurazione
SETPOINT DI LAVORO
primo setpoint di lavoro
secondo setpoint di lavoro
INGRESSI DI MISURA (2)
offset sonda ambiente
tipo di sonda
0 = PTC
1 = NTC
2 = J
3 = K
4 = Pt 100 3 fili
5 = Pt 100 2 fili
6 = Pt 1000 3 fili
7 = Pt 1000 2 fili
8 = 4-20 mA
9 = 0-20 mA
10 = 2-10 V
11 = 0-10 V
12 = 3 wires Ni 120
13 = 2 wires Ni 120
P1
0
1
- - -
1
if P0 = 0 ... 7 or 12 ... 13, decimal point Celsius
degree
1 = YES
if P0 = 8 ... 11, decimal point position
0 = no decimal point
1 = on the digit of ten
P2
0
2
- - -
0
unit of measure temperature (influential only on LED
Celsius degree and on LED Fahrenheit if
P0 = 8 ... 11) (3) (4)
0 = °C
1 = °F
2 = LED Celsius degree and LED Fahrenheit degree
will remain turned off
P3
-199.0 199.0 points
-20.0
minimum value of the range of the transducer
P4
-199.0 199.0 points
80.0
maximum value of the range of the transducer
P5
0
1
- - -
0
quantity to show during the normal operation
0 = room temperature
1 = first working setpoint
PARAM. MIN.
MAX. U.M.
DEF.
REGULATORS
r0
0.1
99.0
°C/°F (1) 2.0
if CFG = 1 or 2, first working setpoint differential
if CFG = 3, differential of the load working for cool-
ing (load 1)
r1
-199.0 r2
°C/°F (1) 0.0
minimum first working setpoint
r2
r1
(5)
°C/°F (1) 350.0 maximum first working setpoint
r3
0
1
- - -
0
locking the first working setpoint modification (with
the procedure related in paragraph 4.1)
1 = YES
r5
0
1
- - -
1
if CFG = 1 or 2, cooling or heating action load 1
if CFG = 4, cooling or heating action loads
0 = cooling
r6
0.1
99.0
°C/°F (1) 2.0
if CFG = 1 or 2, second working setpoint differential
if CFG = 3, differential of the load working for heat-
ing (load 2)
r7
-199.0 r8
°C/°F (1) 0.0
minimum second working setpoint
r8
r7
(5)
°C/°F (1) 350.0 maximum second working setpoint
r9
0
1
- - -
0
locking the second working setpoint modification
(with the procedure related in paragraph 4.2)
1 = YES
r10
0
1
- - -
1
cooling or heating action load 2 (only if CFG = 1 or
2)
0 = cooling
r11
1.0
(5)
°C/°F (1) 5.0
if CFG = 3, neutral zone value
if CFG = 4, value of two steps
PARAM. MIN.
MAX. U.M.
DEF.
LOADS PROTECTIONS
C1
0
240
min
0
minimum time between two activations in succes-
sion of load 1; also load 1 delay since the end of the
room probe error (6)
C2
0
240
min
0
minimum time load 1 remains turned off; also
load 1 delay since you turn on the instrument
C3
0
240
s
0
minimum time load 1 remains turned on
C6
0
1
- - -
0
load 1 activity during the room probe error
0 = turned off
1 = turned on
C7
0
240
min
0
minimum time between two activations in succes-
sion of load 2; also load 2 delay since the end of the
room probe error (6)
C8
0
240
min
0
minimum time load 2 remains turned off; also
load 1 delay since you turn on the instrument
C9
0
240
s
0
minimum time load 2 remains turned on
C10
0
1
- - -
0
load 2 activity during the room probe error
0 = turned off
1 = turned on
PARAM. MIN.
MAX. U.M.
DEF.
TEMPERATURE ALARMS
A1
-199.0 (5)
°C/°F (1) 0.0
temperature the first temperature alarm is activated;
also look at A3 (7)
A2
0
240
min
0
first temperature alarm delay
A3
0
4
- - -
0
kind of first temperature alarm
0 = alarm not enabled
1 = absolute lower alarm (or A1)
2 = absolute upper alarm (or A1)
3 = lower alarm relative to the first working setpoint
(or "first working setpoint - A1”; consider A1 with-
out sign)
4 = upper alarm relative to the first working setpoint
(or "first working setpoint + A1”; consider A1
without sign)
A4
0
240
min
0
temperature alarms delay since an independent
working setpoint modification
A5
-199.0 (5)
°C/°F (1) 0.0
temperature the second temperature alarm is acti-
vated; also look at A7 (7)
9 = 0-20 mA
10 = 2-10 V
11 = 0-10 V
12 = Ni 120 3 fili
13 = Ni 120 2 fili
se P0 = 0 ... 7 o 12 ... 13, punto decimale grado
Celsius
1 = SI
se P0 = 8 ... 11, posizione del punto decimale
0 = nessun punto decimale
1 = sul digit delle decine
unità di misura temperatura (influente solo sul LED
grado Celsius e sul LED grado Fahrenheit se
P0 = 8 ... 11) (3) (4)
0 = °C
1 = °F
2 = il LED grado Celsius e il LED grado Fahrenheit
rimarranno spenti
valore minimo della taratura del trasduttore
valore massimo della taratura del trasduttore
grandezza visualizzata durante il normale funziona-
mento
0 = temperatura dell’ambiente
1 = primo setpoint di lavoro
REGOLATORI
se CFG = 1 o 2, differenziale del primo setpoint di
lavoro
se CFG = 3, differenziale del carico funzionante per
freddo (carico 1)
minimo primo setpoint di lavoro
massimo primo setpoint di lavoro
blocco della modifica del primo setpoint di lavoro
(con la procedura indicata nel paragrafo 4.1)
1 = SI
se CFG = 1 o 2, funzionamento per freddo o per
caldo del carico 1
se CFG = 4, funzionamento per freddo o per caldo
dei carichi
0 = per freddo
se CFG = 1 o 2, differenziale del secondo setpoint di
lavoro
se CFG = 3, differenziale del carico funzionante per
caldo (carico 2)
minimo secondo setpoint di lavoro
massimo secondo setpoint di lavoro
blocco della modifica del secondo setpoint di lavo-
ro (con la procedura indicata nel paragrafo 4.2)
1 = SI
funzionamento per freddo o per caldo del carico 2
(solo se CFG = 1 o 2)
0 = per freddo
se CFG = 3, valore della zona neutra
se CFG = 4, valore di due gradini
PROTEZIONI DEI CARICHI
tempo minimo tra due accensioni consecutive del
carico 1; anche ritardo carico 1 dalla conclusione
dell’errore sonda ambiente (6)
durata minima dello spegnimento del carico 1; an-
che ritardo carico 1 dall’accensione dello strumento
durata minima dell’accensione del carico 1
attività del carico 1 durante l’errore sonda ambiente
0 = spento
1 = acceso
tempo minimo tra due accensioni consecutive del
carico 2; anche ritardo carico 2 dalla conclusione
dell’errore sonda ambiente (6)
durata minima dello spegnimento del carico 2; an-
che ritardo carico 2 dall’accensione dello strumento
durata minima dell’accensione del carico 2
attività del carico 2 durante l’errore sonda ambiente
0 = spento
1 = acceso
ALLARMI DI TEMPERATURA
temperatura alla quale viene attivato il primo allar-
me di temperatura; si veda anche A3 (7)
ritardo primo allarme di temperatura
tipo di primo allarme di temperatura
0 = allarme assente
1 = di minima assoluto (ovvero A1)
2 = di massima assoluto (ovvero A1)
3 = di minima relativo al primo setpoint di lavoro
(ovvero “primo setpoint di lavoro - A1”; consi-
derare A1 senza segno)
4 = di massima relativo al primo setpoint di lavoro
(ovvero “primo setpoint di lavoro + A1”; consi-
derare A1 senza segno)
ritardo allarmi di temperatura dalla modifica di un
setpoint di lavoro indipendente
temperatura alla quale viene attivato il secondo al-
larme di temperatura; si veda anche A7 (7)
ritardo secondo allarme di temperatura
tipo di secondo allarme di temperatura
0 = allarme assente
1 = di minima assoluto (ovvero A5)
2 = di massima assoluto (ovvero A5)
3 = di minima relativo al secondo setpoint di lavoro
(ovvero “secondo setpoint di lavoro - A5”; con-
siderare A5 senza segno) (8)
4 = di massima relativo al secondo setpoint di lavo-
ro (ovvero “secondo setpoint di lavoro + A5”;
considerare A5 senza segno) (8)
INGRESSI DIGITALI
tipo di contatto dell’ingresso digitale
0 = NA (ingresso attivo con contatto chiuso)
1 = NC (ingresso attivo con contatto aperto)
effetto provocato dall'attivazione dell’ingresso
multifunzione
0 = nessun effetto
1 = ATTIVAZIONE ALLARME ESTERNO - trascorso il
tempo i7 il display visualizzerà il codice “iA” lam-
peggiante, il buzzer verrà attivato e l’uscita di
allarme verrà accesa (fino a quando l’ingresso
verrà disattivato)
2 = PROTEZIONE CARICHI - i carichi verranno spen-
ti, il display visualizzerà il codice “iA” lampeg-
giante, il buzzer verrà attivato e l’uscita di allar-
me verrà accesa (fino a quando l’ingresso verrà
disattivato)
se i5 = 1, ritardo segnalazione allarme ingresso
multifunzione
se i5 = 2, ritardo carichi dalla disattivazione dell’in-
gresso multifunzione
RETE SERIALE (MODBUS)
indirizzo strumento
baud rate
0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud
parità
0 = nessuna parità
1 = dispari
2 = pari
RISERVATO
riservato
FUZIONAMENTO
funzionamento
1 = il primo setpoint di lavoro è indipendente e il
secondo è relativo al primo
2 = due setpoint di lavoro indipendenti
3 = zona neutra
4 = due gradini
(1) l’unità di misura dipende dal parametro P2
(2) i valori riportati si riferiscono al modello
EVK403M; nel modello EVK403J il parametro
P0 è impostabile a 2 o 3, il parametro P2 è
impostabile a 0 o 1 e i parametri P3 e P4 non
sono disponibili
(3)
impostare opportunamente i parame-
tri relativi ai regolatori dopo la modi-
fica del parametro P2
(4) se il parametro P0 è impostato a 0 ... 7 o
a 12 ... 13 e il parametro P2 è impostato a 2,
lo strumento funzionerà come se il parametro
P2 fosse impostato a 0
(5) il valore dipende dal parametro P2 (1.300 °C
o 1.999 °F)
(6) se il parametro è impostato a 0, il ritardo dalla
conclusione dell’errore sonda ambiente sarà
comunque di 2 min
(7) il differenziale dipende dal parametro P0
(2,0 °C/4 °F se il parametro P0 è impostato a
0 ... 7 o a 12 ... 13, 2% di P4 - P3 se il parame-
tro P0 è impostato a 8 ... 11)
(8) se il parametro CFG è impostato a 1, 3 o 4, il
secondo allarme di temperatura sarà relativo
al primo setpoint di lavoro (perchè il secondo
setpoint di lavoro è relativo al primo o non è
disponibile).
A6
0
240
min
0
second temperature alarm delay
A7
0
4
- - -
0
kind of second temperature alarm
0 = alarm not enabled
1 = absolute lower alarm (or A5)
2 = absolute upper alarm (or A5)
3 = lower alarm relative to the second working
setpoint (or "second working setpoint - A5”; con-
sider A5 without sign) (8)
4 = upper alarm relative to the second working
setpoint (or "second working setpoint + A5”;
consider A5 without sign) (8)
PARAM. MIN.
MAX. U.M.
DEF.
DIGITAL INPUTS
i1
0
1
- - -
0
kind of contact digital input
0 = NO (input active if you close the contact)
1 = NC (input active if you open the contact)
i5
0
2
- - -
0
effect provoked by the activation of the multipur-
pose input
0 = no effect
1 = ACTIVATING THE EXTERNAL ALARM - spent the
time i7 the display will show the code “iA” flash-
ing, the buzzer will be activated and the alarm
output will be turned on (as long as the input
will be deactivated)
2 = LOADS PROTECTION - the loads will be turned
off, the display will show the code “iA” flash-
ing, the buzzer will be activated and the alarm
output will be turned on (as long as the input
will be deactivated)
i7
0
120
min
0
if i5 = 1, delay to signal the multipurpose input alarm
if i5 = 2, loads delay since the deactivation of the
multipurpose input
PARAM. MIN.
MAX. U.M.
DEF.
SERIAL NETWORK (MODBUS)
LA
1
247
- - -
247
instrument address
Lb
0
3
- - -
2
baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
LP
0
2
- - -
2
parity
0 = none
1 = odd
2 = even
PARAM. MIN.
MAX. U.M.
DEF.
RESERVED
E9
0
1
- - -
1
reserved
PARAM. MIN.
MAX. U.M.
DEF.
OPERATION
CFG
1
4
- - -
1
operation
1 = the first working setpoint is independent and
the second one is relative to the first
2 = two independent working setpoints
3 = neutral zone
4 = two steps
(1)
the unit of measure depends on parameter P2
(2)
the related values refer to model EVK403M; in the model EVK403J parameter P0 can be
set to 2 or 3, parameter P2 can be set to 0 or 1 and parameters P3 and P4 are not
available
(3)
set the parameters related to the regulators appropriately after the
modification of the parameter P2
(4)
if parameter P0 has value 0 ... 7 or 12 ... 13 and parameter P2 has value 2, the
instrument will work as if parameter P2 had value 0
(5)
the value depends on parameter P2 (1,300 °C or 1,999 °F)
(6)
if the parameter has value 0, the delay since the end of the room probe error will
however be 2 min
(7)
the differential depends on parameter P0 (2.0 °C/4 °F if parameter P0 has value 0 ... 7
or 12 ... 13, 2% of P4 - P3 if parameter P0 has value 8 ... 11)
(8)
if parameter CFG has value 1, 3 or 4, the second temperature alarm will be relative to
the first working setpoint (because the first working setpoint is relative to the first or it is
not available).
The instrument must be disposed according to the local legislation about the collection
for electrical and electronic equipment.
Lo strumento deve essere smaltito secondo le normative locali in materia di raccolta
delle apparecchiature elettriche ed elettroniche.