WORKING SETPOINTS AND CONFIGURATION PARAMETERS
8.1 Working setpoints
MIN.
MAX.
U.M.
EVK201
EVK211 WORKING SETPOINTS
r1
r2
°C/°F (1)
0.0
0.0
working setpoint
8.2 Configuration parameters
PARAM. MIN.
MAX.
U.M.
EVK201
EVK211 WORKING SETPOINTS
SP
r1
r2
°C/°F (1)
0.0
0.0
working setpoint
PARAM. MIN.
MAX.
U.M.
EVK201
EVK211 MEASURE INPUTS
CA1
-25.0
25.0
°C/°F (1)
0.0
0.0
cabinet probe offset
P0
0
1
- - -
1
1
kind of probe
0 = PTC
1 = NTC
P1
0
1
- - -
1
1
decimal point Celsius degree (for the quan-
tity to show during the normal operation)
1 = YES
P2
0
1
- - -
0
0
unit of measure temperature (2)
0 = °C
1 = °F
P5
0
1
- - -
not present
0
quantity to show during the normal opera-
tion
0 = cabinet temperature
1 = working setpoint
PARAM. MIN.
MAX.
U.M.
EVK201
EVK211 MAIN REGULATOR
r0
0.1
15.0
°C/°F (1)
2.0
2.0
working setpoint differential
r1
-99.0
r2
°C/°F (1)
-50.0
-50.0
minimum working setpoint
r2
r1
99.0
°C/°F (1)
50.0
50.0
maximum working setpoint
r3
0
1
- - -
not present
0
locking the working setpoint modification
(with the procedure related in paragraph
3.1)
1 = YES
PARAM. MIN.
MAX.
U.M.
EVK201
EVK211 COMPRESSOR PROTECTIONS
C0
0
240
min
0
0
compressor delay since you turn on the in-
strument
C1
0
240
min
not present
5
minimum time between two activations in
succession of the compressor; also compres-
sor delay since the end of the cabinet probe
error (3)
C2
0
240
min
3
3
minimum time the compressor remains
turned off
C3
0
240
s
not present
0
minimum time the compressor remains
turned on
C4
0
240
min
not present
10
time the compressor remains turned off dur-
ing the cabinet probe error; also look at C5
C5
0
240
min
not present
10
time the compressor remains turned on
during the cabinet probe error; also look at
C4
PARAM. MIN.
MAX.
U.M.
EVK201
EVK211 DEFROST
d0
0
99
h
8
8
defrost interval; also look at d8 (5)
0 = the defrost at intervals will never be ac-
tivated
d3
0
99
min
30
30
defrost duration
0 = the defrost will never be activated
d4
0
1
- - -
0
0
defrost when you turn on the instrument
1 = YES
d5
0
99
min
0
0
defrost delay when you turn on the instru-
ment (only if d4 = 1)
d6
0
1
- - -
1
1
temperature shown during the defrost
0 = cabinet temperature
1 = if to the defrost activation the cabinet
temperature is below “working setpoint
+ r0”, at most “working setpoint + r0”; if
to the defrost activation the cabinet tem-
perature is above “working setpoint +
r0”, at most the cabinet temperature to
the defrost activation (6)
d8
0
1
- - -
not present
0
kind of defrost interval
0 = the defrost will be activated when the
instrument will have remained turned
on the time d0
1 = the defrost will be activated when the
compressor will have remained turned
on the time d0
PARAM. MIN.
MAX.
U.M.
EVK201
EVK211 TEMPERATURE ALARMS
A1
-99.0
99.0
°C/°F (1) not present
-10.0
temperature below which the lower tem-
perature alarm is activated; also look at A2
(4)
A2
0
2
- - -
not present
1
kind of lower temperature alarm
0 = alarm not enabled
1 = relative to the working setpoint (or
"working setpoint - A1”; consider A1
without sign)
2 = absolute (or A1)
A4
-99.0
99.0
°C/°F (1) not present
10.0
temperature above which the upper tem-
perature alarm is activated; also look at A5
(4)
A5
0
2
- - -
not present
1
kind of upper temperature alarm
0 = alarm not enabled
1 = relative to the working setpoint (or
"working setpoint + A4”; consider A4
without sign)
2 = absolute (or A4)
A6
0
240
min
not present
120
upper temperature alarm delay since you
turn on the instrument
A7
0
240
min
not present
15
temperature alarm delay
A8
0
240
min
not present
15
upper temperature alarm delay since the end
of the defrost (7)
PARAM. MIN.
MAX. U.M.
EVK201
EVK211 SERIAL NETWORK (MODBUS)
LA
1
247
- - -
not present
247
instrument address
Lb
0
3
- - -
not present
2
baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
LP
0
2
- - -
not present
2
parity
0 = none
1 = odd
2 = even
PARAM. MIN.
MAX. U.M.
EVK201
EVK211 RESERVED
E9
0
1
- - -
not present
1
reserved
(1)
the unit of measure depends on parameter P2
(2)
set the parameters related to the regulators appropriately after the
modification of the parameter P2
(3)
if parameter C1 has value 0, the delay since the end of the cabinet probe error will
however be 2 min
(4)
the differential of the parameter is 2.0 °C/4 °F
(5)
the instrument stores the count of the defrost interval every 30 min (only EVK211); the
modification of parameter d0 has effect since the end of the previous defrost interval or since
the activation of a defrost by hand
(6)
the display restores the normal operation as soon as the defrost ends and the cabinet
temperature falls below the one that has locked the display (or if a temperature alarm
arises)
(7)
during the defrost the temperature alarms are not enabled, on condition that they have
arisen after the activation of the defrost.
The instrument must be disposed according to the local legislation about the collection for
electrical and electronic equipment.
Lo strumento deve essere smaltito secondo le normative locali in materia di raccolta delle
apparecchiature elettriche ed elettroniche.
I ITALIANO
8
SETPOINT DI LAVORO E PARA-
METRI DI CONFIGURAZIONE
8.1 Setpoint di lavoro
SETPOINT DI LAVORO
setpoint di lavoro
8.2 Parametri di configurazione
SETPOINT DI LAVORO
setpoint di lavoro
INGRESSI DI MISURA
offset sonda cella
tipo di sonda
0 = PTC
1 = NTC
punto decimale grado Celsius (per la gran-
dezza visualizzata durante il normale funzio-
namento)
1 = SI
unità di misura temperatura (2)
0 = °C
1 = °F
grandezza visualizzata durante il normale fun-
zionamento
0 = temperatura della cella
1 = setpoint di lavoro
REGOLATORE PRINCIPALE
differenziale del setpoint di lavoro
minimo setpoint di lavoro
massimo setpoint di lavoro
blocco della modifica del setpoint di lavoro
(con la procedura indicata nel paragrafo 3.1)
1 = SI
PROTEZIONI DEL COMPRESSORE
ritardo compressore dall’accensione dello stru-
mento
tempo minimo tra due accensioni consecuti-
ve del compressore; anche ritardo compres-
sore dalla conclusione dell’errore sonda cella
(3)
durata minima dello spegnimento del com-
pressore
durata minima dell’accensione del compres-
sore
durata dello spegnimento del compressore
durante l’errore sonda cella; si veda anche
C5
durata dell’accensione del compressore du-
rante l’errore sonda cella; si veda anche C4
SBRINAMENTO
intervallo di sbrinamento; si veda anche d8
(5)
0 = lo sbrinamento a intervalli non verrà mai
attivato
durata dello sbrinamento
0 = lo sbrinamento non verrà mai attivato
sbrinamento all’accensione dello strumento
1 = SI
ritardo sbrinamento dall’accensione dello stru-
mento (solo se d4 = 1)
temperatura visualizzata durante lo
sbrinamento
0 = temperatura della cella
1 = se all’attivazione dello sbrinamento la
temperatura della cella è al di sotto di
“setpoint di lavoro + r0”, al massimo
“setpoint di lavoro + r0”; se all’attivazio-
ne dello sbrinamento la temperatura
della cella è al di sopra di “setpoint di
lavoro + r0”, al massimo la temperatura
della cella all’attivazione dello
sbrinamento (6)
tipo di intervallo di sbrinamento
0 = lo sbrinamento verrà attivato quando lo
strumento sarà rimasto acceso per il tem-
po d0
1 = lo sbrinamento verrà attivato quando il
compressore sarà rimasto acceso per il
tempo d0
ALLARMI DI TEMPERATURA
temperatura al di sotto della quale viene atti-
vato l’allarme di temperatura di minima; si
veda anche A2 (4)
tipo di allarme di temperatura di minima
0 = allarme assente
1 = relativo al setpoint di lavoro (ovvero
“setpoint di lavoro - A1”; considerare A1
senza segno)
2 = assoluto (ovvero A1)
temperatura al di sopra della quale viene at-
tivato l’allarme di temperatura di massima; si
veda anche A5 (4)
tipo di allarme di temperatura di massima
0 = allarme assente
1 = relativo al setpoint di lavoro (ovvero
“setpoint di lavoro + A4”; considerare A4
senza segno)
2 = assoluto (ovvero A4)
ritardo allarme di temperatura di massima dal-
l’accensione dello strumento
ritardo allarme di temperatura
ritardo allarme di temperatura di massima
dalla conclusione dello sbrinamento (7)
RETE SERIALE (MODBUS)
indirizzo strumento
baud rate
0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud
parità
0 = nessuna parità
1 = dispari
2 = pari
RISERVATO
riservato
(1) l’unità di misura dipende dal parame-
tro P2
(2)
impostare opportunamente i pa-
rametri relativi ai regolatori dopo
la modifica del parametro P2
(3) se il parametro C1 è impostato a 0, il
ritardo dalla conclusione dell’errore son-
da cella sarà comunque di 2 min
(4) il differenziale del parametro è di 2,0 °C/
4 °F
(5) lo strumento memorizza il conteggio
dell’intervallo di sbrinamento ogni 30
min (solo EVK211); la modifica del pa-
rametro d0 ha effetto dalla conclusio-
ne del precedente intervallo di
sbrinamento o dall’attivazione di uno
sbrinamento in modo manuale
(6) il display ripristina il normale funziona-
mento quando, concluso lo
sbrinamento, la temperatura della cella
scende al di sotto di quella che ha bloc-
cato il display (o se si manifesta un allar-
me di temperatura)
(7) durante lo sbrinamento gli allarmi di
temperatura sono assenti, a condizio-
ne che questi si siano manifestati dopo
l’attivazione dello sbrinamento.