Disconnect handle installation – Rockwell Automation 1494C-xxx Cable Operated 600A Disconnect Switch Manuale d'uso
Pagina 2

PN-133649
DIR 42052-191 (Version 03)
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Go to Installation Instruction Sheet 42052-190-01.
Trailer Fuse Block Installation
5
Cable Mechanism Installation
3
ATTENTION: Check for proper operation. Upon successful completion of the installation instructions no further
adjustment of the cable mechanism is required.
1
Verify that disconnect switch and handle are in the
"ON" position.
Rotate connecting rod (clockwise) into drive bar until
it begins to exit the drive bar (approximately 18 full
turns).
C
L
O
S
E
D
3
5
4
Align connecting rod with primary link.
Turn disconnect handle "OFF" and install handle mechanism spring.
Install hitch pin clip.
Hitch Pin Clip
90 - 130 lb-in
(4) - 5/16-18 thread
forming screws
provided with
disconnect switch.
7
Assemble disconnect switch assembly to mounting plate.
Disconnect Handle Installation
Install gasket.
1
2
3
2
2
7 - 11 lb-in
Install handle and mechanism bracket.
Install defeater lever.
(Right Hand
Flange Mounted
Shown)
60 - 80 lb-in
6
Attach threaded rod to cable mechanism lever.
Threaded
Rod
Cable
Mechanism
Lever
90 - 130 lb-in
90 - 130 lb-in
IMPORTANT: Apply grease to O-Ring
to retain into handle groove.
Primary Link
Connecting
Rod
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1494C-IN006C-EN-E - January 2013
1
2