Xylem GEN series firefighting booster sets Manuale d'uso
Pagina 32

en
32
WARNING
9. Repair – Spare parts
Repairs must be made by qualified personnel using original spare parts.
See also the diesel pump’s manual.
10. Pumpset troubleshooting guide
All maintenance and repair operations must be performed by qualified personnel.
Before servicing the set, disconnect the power supply.
Before servicing the set, make sure there is no pressure in the hydraulic
components.
For sets with diesel pump, see also the handbook supplied with the diesel
pump.
Problem
Cause
Solution
1. Set is off
1. Power supply disconnected Connect the power supply
2. Fuse blown
Replace the fuse
2. Motor does not
start
1. Power supply disconnected Connect the power supply
2. Fuse blown
Replace the fuse
3. Panel’s automatic switch
Reset the automatic switch
4. Defective motor
Repair/replace motor
3. The motor runs
but no water is
delivered
1. No water on suction side or
inside pump
Fill the pump or suction
piping / open the on-off
valves
2. Air in suction piping or
pump
Bleed the pump, check the
suction connections
3. Loss of pressure on suction
side
Check the NPSH and, if
necessary, modify the system
4. Check valve jammed
Clean the valve
5. Clogged pipe
Clean the pipe
6. Incorrect rotation of three-
phase motors
Change direction of rotation
4. Pump leaks
water
1. Defective mechanical seal
Replace the mechanical seal
2. Undue mechanical stress on
pump
Support the pipes
5. Too noisy
1. Water return when pumps
stop
Check the check valve
2. Cavitation
Check suction
3. Pump rotation hindered
Check for undue mechanical
stress on pump
INFORMATION FOR INSTALLERS AND USERS
WARNING