WARNING


9. Repair – Spare parts

Repairs must be made by qualified personnel using original spare parts.
See also the diesel pump’s manual.

10. Pumpset troubleshooting guide

All maintenance and repair operations must be performed by qualified personnel.
Before servicing the set, disconnect the power supply.


Before servicing the set, make sure there is no pressure in the hydraulic
components.

For sets with diesel pump, see also the handbook supplied with the diesel
pump.

Problem

Problem

Problem

Problem

Cause

Cause

Cause

Cause

Solution

Solution

Solution

Solution

1. Power supply disconnected

Connect the power supply

1. Set is off

2. Fuse blown

Replace the fuse

1. Power supply disconnected

Connect the power supply

2. Fuse blown

Replace the fuse

3. Panel’s automatic switch

Reset the automatic switch

2. Motor does not
start

4. Defective motor

Repair/replace motor

1. No water on suction side or

inside pump

Fill the pump or suction
piping / open the on-off
valves

2. Air in suction piping or

pump

Bleed the pump, check the
suction connections

3. Loss of pressure on suction

side

Check the NPSH and, if
necessary, modify the system

4. Check valve jammed

Clean the valve

5. Clogged pipe

Clean the pipe

3. The motor runs
but no water is
delivered

6. Incorrect rotation of three-

phase motors

Change direction of rotation

1. Defective mechanical seal

Replace the mechanical seal

4. Pump leaks
water

2. Undue mechanical stress on

pump

Support the pipes

1. Water return when pumps

stop

Check the check valve

2. Cavitation

Check suction

5. Too noisy

3. Pump rotation hindered

Check for undue mechanical
stress on pump

INFORMATION FOR INSTALLERS AND USERS

WARNING