Diagramma funzionale e parametri pa – VEGA VEGASON 51P…53P Profibus PA Manuale d'uso
Pagina 74

74
VEGASON 51P … 53P
Diagramma funzionale e parametri PA
Slot Index
Parameter
Object
Read Write
Type
Size
Reset value
Store
Unit
Optional
manda-
tory
0
38 Device install date
PB
si
si
OctetString
16 -
S
o
0
40 Ident number select
PB
si
si
Unsigned8
1 -
S
m
0
41 HW write protection
PB
si
no
Unsigned8
1
D
o
0
49 VVO
PB
si
si
OctetString
32
o
0
50 View object PB
PB
si
no
OctetString
17
D
m
1
0
Directory
object header
DM
si
no
Array of
Unsigned16
12
C
m
1
1
Composite list
directory entries
DM
si
no
Array of
Unsigned16
24
C
m
1
16 Block object
FB_Primary_Value
si
no
DS-32
20
C
m
1
17 St rev
FB_Primary_Value
si
no
Unsigned16
2 0
N
m
1
18 Tag desc
FB_Primary_Value
si
si
OctetString
32 32 * ' '
S
m
1
19 Strategy
FB_Primary_Value
si
si
Unsigned16
2 0
S
m
1
20 Alert key
FB_Primary_Value
si
si
Unsigned8
1 0
S
m
1
21 Target mode
FB_Primary_Value
si
si
Unsigned8
1 8
S
m
1
22 Mode blk
FB_Primary_Value
si
no
DS-37
3
D
m
1
23 Alarm sum
FB_Primary_Value
si
no
DS-42
8
D
m
1
24 Batch
FB_Primary_Value
si
si
DS-67
10 0,0,0,0
S
m
1
26 Out
FB_Primary_Value
si
si (*1)
DS-33
5
D
out scale unit
m
1
27 PV scale
FB_Primary_Value
si
si
2 * Float
8 0,100
S
prim, sec1,
sec2 value unit
(dep. on channel)
m
1
28 Out scale
FB_Primary_Value
si
si
DS-36
11 0,100,-,-
S
includes
out scale unit
m
1
29 Lin type
FB_Primary_Value
si
si (*1)
Unsigned8
1 0
S
m
1
30 Channel
FB_Primary_Value
si
si
Unsigned16
2 -
S
m
1
32 PV FTime
FB_Primary_Value
si
si
Float
4 0
N
sec
m
1
33 Fsafe type
FB_Primary_Value
si
si
Unsigned8
1 1
S
o
1
34 Fsafe value
FB_Primary_Value
si
si
Float
4 -
S
out scale unit
o
1
35 Alarm hys
FB_Primary_Value
si
si
Float
4 0.5% of range S
out scale unit
m
1
37 HI HI Lim
FB_Primary_Value
si
si
Float
4 max value
S
out scale unit
m
1
39 HI Lim
FB_Primary_Value
si
si
Float
4 max value
S
out scale unit
m
1
41 LO Lim
FB_Primary_Value
si
si
Float
4 min value
S
out scale unit
m
1
43 LO LO Lim
FB_Primary_Value
si
si
Float
4 min value
S
out scale unit
m
1
46 HI HI Alm
FB_Primary_Value
si
no
DS-39
16 0
D
o
1
47 HI Alm
FB_Primary_Value
si
no
DS-39
16 0
D
o
1
48 LO Alm
FB_Primary_Value
si
no
DS-39
16 0
D
o
1
49 LO LO Alm
FB_Primary_Value
si
no
DS-39
16 0
D
o
1
50 Simulate
FB_Primary_Value
si
si
DS-50
6 disable
N
prim, sec1, sec2
value unit
(dep. on channel)
m
1
61
View object
FB_Primary_Value
FB_Primary_Value
si
no
OctetString
18
D
m
1
180 Display source select TB
si
si
Unsigned8
1 ?
N
o