2 technical data, Technical data 2 – Lenze EZS3-xxxA200 Sinusoidal filter 4-90A Manuale d'uso
Pagina 21

Technical data 2
EDKZS3X200 DE/EN/FR/ES/IT 1.1
21
H1daten-BemessdatSF
2
Technical data
Standards
Conformity
CE
Low-Voltage Directive
Approval
UR
UL508, Industrial Control
Equipment, Underwriter
Laboratories (File-No. E219022)
for USA and Canada
Operating conditions
Climatic conditions
Class 3K3 according to EN 50178 Without condensation, average
relative humidity 85 %
Permissible ambient
operating temperature
-10 °C ... +55 °C
Above 40 °C, the rated current I
N
must be reduced by 2.5 %/°C
Permissible installation
height
0 ... 4000 m amsl
Above 1000 m, the rated current I
N
must be reduced by 5 %/1000 m
Vibration resistance
Accelerational stability up to 1 g
EN50178, IEC61800-5-1 and
Germanischer Lloyd, general
conditions
Degree of protection
IP20 (protection against contact to NEMA 250 type 1)
Mounting position
Vertical with fixing bracket below
Depending on the weight, wall mounting is possible
Connecting cables
Drive controller ↔ filter As short as possible, shielded
Filter ↔ motor Max. 200 m shielded or max. 300 m unshielded