Report unit number, Assign unit number, Set number of floats – VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions Manuale d'uso
Pagina 70: Set baud rate

70
10 Appendice
VEGABAR 87 • Protocollo Modbus e LevelMaster
46297-IT
-131205
Report Unit Number
Request:
Parametro
Length
Code/Data
Report Unit Number
5 characters ASCII
U**N?
Response:
Parametro
Length
Code/Data
Report Level (and Temperature)
6 characters ASCII
UuuNnn
Assign Unit Number
Request:
Parametro
Length
Code/Data
Assign Unit Number
6 characters ASCII
UuuNnn
Response:
Parametro
Length
Code/Data
Assign Unit Number
6 characters ASCII
UuuNOK
uu = new Address
Set number of Floats
Request:
Parametro
Length
Code/Data
Set number of Floats
5 characters ASCII
UuuFn
Response:
Parametro
Length
Code/Data
Set number of Floats
6 characters ASCII
UuuFOK
Se il numero viene impostato su 0, non viene più segnalato alcun livello
Set Baud Rate
Request:
Parametro
Length
Code/Data
Set Baud Rate
8 (12) characters ASCII
UuuBbbbb[b][pds]
Bbbbb[b] = 1200, 9600 (default)
pds = parity, data length, stop bit
(optional)
parity: none = 81, even = 71 (defau-
lt), odd = 71