5 comandi levelmaster, Fc43 sub 14, read device identification, Parametri per la comunicazione bus – VEGA VEGAPULS 65 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol Manuale d'uso
Pagina 62

62
11 Appendice
VEGAPULS 65 • Protocollo Modbus e LevelMaster
41365-IT
-121116
Parametri
Length
Code/Data
Run Indicator Status
1 Byte
FC43 Sub 14, Read Device Identification
Con questo codice di funzione può essere richiesta la Device Identification.
Request:
Parametri
Length
Code/Data
Function Code
1 Byte
0x2B
MEI Type
1 Byte
0x0E
Read Device ID Code
1 Byte
0x01 to 0x04
Object ID
1 Byte
0x00 to 0xFF
Response:
Parametri
Length
Code/Data
Function Code
1 Byte
0x2B
MEI Type
1 Byte
0x0E
Read Device ID Code
1 Byte
0x01 to 0x04
Confirmity Level
1 Byte
0x01, 0x02, 0x03, 0x81, 0x82, 0x83
More follows
1 Byte
00/FF
Next Object ID
1 Byte
Object ID number
Number of Objects
1 Byte
List of Object ID
1 Byte
List of Object length
1 Byte
List of Object value
1 Byte
Depending on the Object ID
11.5 Comandi LevelMaster
Il VEGAPULS 65 è idoneo anche ad essere collegato ai seguenti RTU con protocollo LevelMaster.
Questo protocollo viene spesso designato come "Protocollo Siemens" o "Protocollo serbatoio".
RTU
Protocol
ABB Totalflow
Levelmaster
Kimray DACC 2000/3000
Levelmaster
Thermo Electron Autopilot
Levelmaster
Parametri per la comunicazione bus
Nel VEGAPULS 65 sono preimpostati valori di default:
Parametri
Configurable Values
Default Value
Baud Rate
1200, 2400, 4800, 9600, 19200
9600
Start Bits
1
1
Data Bits
7, 8
8
Parity
None, Odd, Even
None