5 comandi levelmaster, Fc43 sub 14, read device identification, Parametri per la comunicazione bus – VEGA VEGAFLEX 83 Modbus and Levelmaster protocol Polished version Manuale d'uso
Pagina 83

83
11 Appendice
VEGAFLEX 83 • Protocollo Modbus e LevelMaster
41843-IT
-130416
Response:
Parametri
Length
Code/Data
Function Code
1 Byte
0x11
Byte Number
1 Byte
Slave ID
1 Byte
Run Indicator Status
1 Byte
FC43 Sub 14, Read Device Identification
Con questo codice di funzione può essere richiesta la Device Identification.
Request:
Parametri
Length
Code/Data
Function Code
1 Byte
0x2B
MEI Type
1 Byte
0x0E
Read Device ID Code
1 Byte
0x01 to 0x04
Object ID
1 Byte
0x00 to 0xFF
Response:
Parametri
Length
Code/Data
Function Code
1 Byte
0x2B
MEI Type
1 Byte
0x0E
Read Device ID Code
1 Byte
0x01 to 0x04
Confirmity Level
1 Byte
0x01, 0x02, 0x03, 0x81, 0x82, 0x83
More follows
1 Byte
00/FF
Next Object ID
1 Byte
Object ID number
Number of Objects
1 Byte
List of Object ID
1 Byte
List of Object length
1 Byte
List of Object value
1 Byte
Depending on the Object ID
11.5 Comandi LevelMaster
Il VEGAFLEX 83 è idoneo anche ad essere collegato ai seguenti RTU con protocollo LevelMaster.
Questo protocollo viene spesso designato come "Protocollo Siemens" o "Protocollo serbatoio".
RTU
Protocol
ABB Totalflow
Levelmaster
Kimray DACC 2000/3000
Levelmaster
Thermo Electron Autopilot
Levelmaster
Parametri per la comunicazione bus
Nel VEGAFLEX 83 sono preimpostati i valori di default: